14
3. HOW TO OPERATE [Setting of the Control Functions]
When the power is instantaneously interrupted and then
uninterrupted, the air compressor and the air dryer start
simultaneously.
IMPORTANT
When you use an external automatic control
panel (multiple-unit controller, two-unit controller, etc.):
・
Set the DIP switch
SW2
No.1 & 2 to ON & ON
respectively (to enable the manual mode), and
the DIP switch
SW1
No.1 to OFF (to disable
the air dryer prestart function).
Thus you can protect the air dryer from stopping
and restating frequently.
CAUTION
3.4.4 Setting of Air Dryer
(1) Operation Modes
As listed in the table left, the models with a built-in
air dryer provide 3 operation modes. You can select
either one of them by setting the No. 1 & 2 pins of the
DIP switch
SW2
located on the printed circuit board.
If you want to enable an air dryer prestart function,
always select the automatic mode.
If you want to start and stop the built-in air dryer with
the
DRYER
button, always select the manual mode.
The settings are saved in the memory when you have
stopped the
A
.
(2) Air Dryer Prestarting
To enable the air dryer prestart function, set:
DIP switch
SW2
No.1 & 2 to ON & OFF respec-
tively, and
DIP switch
SW1
No.1 to ON.
When you press the
START
button under the air dryer
prestart function,
・
The
START
light and
DRYER
light become on (non-
flashing),
・
The
AUTO START
light becomes on (flashing), and
・
The air dryer prestarts.
Three minutes later,
・
The
AUTO START
light becomes off, and
・
The air compressor automatically starts.
This chills the built-in air dryer sufficiently in advance,
and thus enables to discharge the dry compressed air
from the beginning.
NOTE: The shaded cells indicate a standard factory setting.
This page describes for the models with a
built-in air dryer.
No.1
OFF
OFF
ON
ON
No.2
OFF
ON
OFF
ON
–
Independent Automatic
Manual
DRYER Light
OFF
Without
Built-in
Air Dryer
With Built-in Air Dryer
DIP Switch
SW2
Air Dryer
Operation Mode
(by connecting
& disconnect-
ing the power)
(by START
and STOP
buttons)
(by DRYER
button)
ON (non-flashing) for normal operation
ON (flashing) for abnormal operation
A
Models
1
6
CN16
51
CN17
41
CN8
21
CN2
19
CN1
17
CN15
17
Y3
Y1
Y1
CPU
Y52C
Y2D
Y52
CN13
1
3
CN3
1
5
CN5
1
7
CN4
1
7
CN6
1
5
CN14
4
1
Y42
Y6
C38
C4D
C39
ICO
GND
CN11
CN12
1
4
CN18
1
3
CN19
1
3
CN22
1
4
CN21
1
5
1
2
CN10
1
1
8
2
CN9
SW1
1
4
SW2
CN7
HC30CPU−
SW1
ON
OFF
DIP Switch
③
1 2
2
Air Dryer Alarming
Air Dryer Shutdown
Operation Mode
(indicates the automatic mode.)
ON
OFF
Air Dryer Prestarting
SW2
1
4
ON
OFF
DIP Switch
Printed Circuit Board
②
④
①
Power
Supply
(3) Air Dryer Warning (Shutdown/Alarm)
To enable the air dryer warning function, set the DIP
switch
SW1
No.2 to:
ON for an alarm, and
OFF for a shutdown.
When the air dryer fails,
・
The
SHUTDOWN
or
ALARM
light becomes on
(flashing),
・
The
DRYER
light begins flashing, and
・
The digital monitor displays the shutdown or alarm
code.
When the
SHUTDOWN
light flashes, the air compres-
sor is automatically shut down. When the
ALARM
light
flashes, the air compressor is not shut down but keeps
operating. In either case, usually, the air dryer is shut
down.
(4) Setting Procedure
When setting the DIP switches
SW1
and
SW2
:
q
Disconnect the power.
w
Detach the door (for the 22 kW models) or the front
enclosure panel (for the 37 kW models), and then
remove the starter/control box cover.
e
Set the DIP switches
SW1
and
SW2
as required.
r
Return the door or front enclosure panel and the