Configuring Drive Parameters
18
C” Group: Intelligent Terminal Functions
The intelligent input terminals for L100-M Series inverters have 21 possible option
assignments.
L100-M Series inverters have the 15 intelligent input option codes of standard L100
inverters, but with the model series restriction noted below:
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name /
SRW Display
Description
–MFU2
–MFR2
Units
C_01 Terminal [1] function
Select function for terminal [1]
21 options (see next section)
✘
00
[FW]
00
[FW]
—
IN-TM 1 FW
C_02 Terminal [2] function
Select function for terminal [2]
21 options (see next section)
✘
01
[RV]
01
[RV]
—
IN-TM 2 RV
C_03 Terminal [3] function
Select function for terminal [3]
21 options (see next section)
✘
16
[AT]
02
[CF1]
—
IN-TM 3 AT
C_04 Terminal [4] function
Select function for terminal [4]
21 options (see next section)
✘
13
[USP]
03
[CF2]
—
IN-TM 4 USP
C_05 Terminal [5] function
Select function for terminal [5]
21 options (see next section)
✘
18
[RS]
18
[RS]
—
IN-TM 5 2CH
Input Function Summary Table
Option
Code
Terminal
Symbol
Function Name
Description
19
PTC
PTC Thermistor
Thermal Protection
–MFR2 series only
ON
When a thermistor is connected to terminals [5]
and [L], the inverter checks for over-
temperature and will cause trip event and turn
OFF output to motor
OFF
A disconnect of the thermistor causes a trip
event, and the inverter turns OFF the motor