Using Intelligent Output Terminals
Oper
ations
and Monitor
ing
4–22
Run Signal
When the [RUN] signal is selected as an
intelligent output terminal, the inverter
outputs a signal on that terminal when it is in
Run Mode. The output logic is active low, and
is the open collector type (switch to ground).
NOTE:
The example circuit in the table above drives a relay coil. Note the use of a
diode to prevent the negative-going turn-off spike generated by the coil from damaging
the inverter’s output transistor.
[FW],
[RV]
Output
freq.
Run
Signal
start freq.
B 82
t
ON
1
0
1
0
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
00
RUN
Run Signal
ON
when inverter is in Run Mode
OFF
when inverter is in Stop Mode
Valid for outputs:
11, 12
Required settings:
(none)
Notes:
•
The inverter outputs the [RUN] signal whenever the
inverter output exceeds the start frequency specified
by parameter B_82
.
The start frequency is the initial
inverter output frequency when it turns ON.
Example (default output configuration
shown—see page
RY
+
–
See I/O specs on page
12 11
L
H O OI
FM CM2
RUN
Inverter output
terminal circuit