L100 Inverter
Conf
igur
ing
Dr
iv
e P
a
ra
m
e
ters
3–5
Operational Modes
The RUN and PGM LEDs tell just part of the story;
Run Mode and Program Modes are independent
modes, not opposite modes. In the state diagram to
the right, Run alternates with Stop, and Program
Mode alternates with Monitor Mode. This is a very
important ability, for it shows that a technician can
approach a running machine and change some
parameters without shutting down the machine.
The occurrence of a fault during operation will
cause the inverter to enter the Trip Mode as shown.
An event such as an output overload will cause the
inverter to exit the Run Mode and turn OFF its
output to the motor. In the Trip Mode, any request
to run the motor is ignored. You must clear the
error by pressing the Stop/Reset switch. See page
“Monitoring Trip Events, History, & Conditions”
on page 6–5
Run Mode Edits
The inverter can be in Run Mode (inverter output is controlling motor) and still allow
you to edit certain parameters. This is useful in applications that must run continuously,
yet need some inverter parameter adjustment.
The parameter tables in this chapter have a column titled “Run
Mode Edit.” An Ex mark
✘
means the parameter cannot be
edited; a Check mark
✔
means the parameter can be edited.
The Software Lock Setting (parameter B_31) determines when
the Run Mode access permission is in effect and access
permission in other conditions, as well. It is the responsibility
of the user to choose a useful and safe software lock setting for
the inverter operating conditions and personnel. Please refer to
“Software Lock Mode” on page 3–26
for more information.
Control Algorithms
The motor control program in the L100
inverter has two PWM sinusoidal switching
algorithms. The intent is that you select the
best algorithm for the motor characteristics
in your application. Both algorithms
generate the frequency output in a unique
way. Once configured, the algorithm is the
basis for other parameter settings as well
(see
“Torque Control Algorithms” on
). Therefore, choose the best
algorithm early in your application design
process.
RUN
STOP
RESET
FUNC.
Run
Stop
Monitor
Program
RUN
STOP
RESET
STOP
RESET
Run
Stop
Trip
Fault
Fault
Run
Mode
Edit
✘
✔
Output
Variable freq. control,
constant torque
Variable freq. control,
reduced torque
Inverter Control Algorithms