L100 Inverter
Oper
ations
and Monitor
ing
4–23
Frequency Arrival Signals
The
Frequency Arrival
group of outputs help coordinate external systems with the
current velocity profile of the inverter. As the name implies, output [FA1] turns ON
when the output
frequency arrives
at the standard set frequency (parameter F_01).
Output [FA2] relies on programmable accel/ decel thresholds for increased flexibility.
For example, you can have an output turn ON at one frequency during acceleration, and
have it turn OFF at a different frequency during deceleration. All transitions have hyster-
esis to avoid output chatter if the output frequency is near one of the thresholds.
Option
Code
Terminal
Symbol
Function Name
Output
State
Description
01
FA1
Frequency Arrival
Type 1 – Constant
Speed
ON
when output to motor is at the set frequency
OFF
when output to motor is OFF, or in any accelera-
tion or deceleration ramp
02
FA2
Frequency Arrival
Type 2 – Over-
frequency
ON
when output to motor is at or above the set
frequency thresholds for, even if in acceleration
or deceleration ramps
OFF
when output to motor is OFF, or during accelera-
tion or deceleration before the respective thresh-
olds are crossed
Valid for outputs:
11, 12
Required settings:
(none)
Notes:
•
For most applications you will need to use only one
type of frequency arrival outputs (see examples).
However, it is possible assign both output terminals
to output functions [FA1] and [FA2].
•
For each frequency arrival threshold, the output
anticipates the threshold (turns ON early) by 1.5Hz.
•
The output turns OFF as the output frequency
moves away from the threshold, delayed by 0.5Hz.
•
The delay time of the output signal is 60 ms
(nominal).
Example (default output configuration
shown—see page
See I/O specs
on page
RY
+
–
Inverter output
terminal circuit
FA1
12 11
L
H O OI
FM CM2