L200
2
Inverter
Appendix B
B–41
C081
O input span calibration
R/W Scale factor between the
external frequency command
on terminals L – O (voltage
input) and the frequency
output, range is 0.0 to 200.0%
1141h
04417 0 to 2000
0.1 %
C082
OI input span calibra-
tion
R/W Scale factor between the
external frequency command
on terminals L – OI (current
input) and the frequency
output, range is 0.0 to 200.0%
1142h
04418 0 to 2000
0.1 %
C085
Thermistor input tuning
R/W Range is 0.0 to 200.0%
1144h
04420 0 to 2000
0.1 %
C086
[AM] terminal offset
tuning
R/W Range is 0.0 to 10.0V
1145h
04421
0 to 100
0.1 V
C091
Debug mode enable
R
Displays debug parameters.
Two option codes:
00... Disable
01... Enable
1148h
04424
0, 1
—
C101
Up/Down memory
mode
selection
R/W Controls speed setpoint for
the inverter after power cycle.
Two option codes:
00... Clear last frequency
(return to default frequency
F001)
01... Keep last frequency
adjusted by UP/DWN
1149h
04425
0, 1
—
C102
Reset selection
R/W Determines response to Reset
input [RST].
Three option codes:
00... Cancel trip state at input
signal ON transition, stops
inverter if in Run Mode
01... Cancel trip state at signal
OFF transition, stops inverter
if in Run Mode
02... Cancel trip state at input
signal ON transition, no effect
if in Run Mode
114Ah 04426
0, 1, 2
—
C141
Input A select for logic
output
R/W
See
1150h
04432 0, 1, 2, 3,
4, 5, 6, 7,
8, 9
—
C142
Input B select for logic
output
R/W
1151h
04433
“C” Group Intelligent Terminal Functions
Func.
Code
Name
R/W
Description
Network Data
Register
Range
Res.
hex
dec.