L200
2
Inverter
Appendix B
B–19
ModBus Data Listing
ModBus Coil List
The following tables list the primary coils for the inverter interface to the network. The
table legend is given below.
•
Coil Number -
The network
register address offset
for the coil, in hex and decimal.
Actual network address is 30001 + offset. The coil data is a single bit (binary) value.
•
Name -
The functional name of the coil
•
R/W -
The read-only (R) or read-write (R/W) access permitted to the inverter data
•
Description -
The meaning of each of the states of the coils
List of Coil Numbers
Coil Number
Name
R/W
Description
hex
dec.
0000h
00000 (Reserved)
R
—
0001h
00001 Run command
R/W
0 .... Stop
1 .... Run (enabled when A003=03)
0002h
00002 FW/REV command
R/W
0 .... REV
1 .... FW (enabled when A003=03)
0003h
00003 External trip (EXT)
R/W
0 .... No trip event
1 .... Trip occurred
0004h
00004 Trip reset (RS)
R/W
0 .... No reset condition
1 .... Reset
0005h
00005 (Reserved)
R
—
0006h
00006 (Reserved)
R
—
0007h
00007 Intelligent input terminal 1
R/W
0 .... OFF *1
1 .... ON
0008h
00008 Intelligent input terminal 2
R/W
0009h
00009 Intelligent input terminal 3
R/W
000Ah 00010 Intelligent input terminal 4
R/W
000Bh 00011 Intelligent input terminal 5
R/W
000Dh 00013 (Not used)
—
—
000Eh
00014 Run/Stop status
R
0 .... Stop (corresponds to D003
monitor)
1 .... Run
000Fh
00015 FW/REV status
R
0 .... FW
1 .... RV
0010h
00016 Inverter ready
R
0 .... Not ready
1 .... Ready
0011h
00017 (Reserved)
R
—
0012h
00018 (Reserved)
R
—
Summary of Contents for L200-002NFE2
Page 2: ......
Page 46: ......
Page 80: ......
Page 204: ......
Page 212: ......
Page 229: ...Glossary and Bibliography In This Appendix page Glossary 2 Bibliography 8 A ...
Page 280: ......
Page 297: ...L2002 Inverter Appendix D D 5 L1 L2 L3 PE L2002 inverter with book type filter M 3 ...