SPECIFICATIONS
1-2
1.1. MULTIZONE INDOOR
1.1.1. WALL TYPE (RAK-15QEF, RAK-18REF, RAK-25REF)
INDOOR
Unit
RAK-15QEF
RAK-18REF
RAK-25REF
Nominal capacity adjustable
no
no
no
Nominal Cooling capacity
(min - max)
kW
1.50 (0.90- 2.00)
2.00 (0.90 - 2.50)
2.50 (0.90 - 3.10)
Cooling sensible capacity
kW
Nominal Heating capacity
(min - max)
kW
2.00 (1.00 - 2.50)
2.50 (0.90 - 3.20)
3.40 (0.90- 4.40)
Noise level cooling (sound pressure)
(SL / L / M / H)
dB(A)
21 / 24 / 33 / 37
21 / 24 / 33 / 37
22 / 24 / 33 / 40
Noise level heating (sound pressure)
(SL / L / M / H)
dB(A)
19 / 22 / 33 / 38
19 / 22 / 33 / 38
20 / 23 / 34 / 41
Noise level (sound power)
dB(A)
52
52
54
Air flow cooling mode (SL / L / M / H)
m
3
/h
312 / 350 / 400 / 440
312 / 350 / 400 / 440
333 / 370 / 430 / 510
Air flow heating mode (SL / L / M / H)
m
3
/h
312 / 350 / 420 / 480
312 / 350 / 420 / 480
333 / 400 / 500 / 570
Fan Motor
W
38
38
38
Dehumidification
l/h
1.2
1.2
1.4
Dimensions (H x W x D)
mm
280 x 780 x 215
280 x 780 x 215
280 x 780 x 215
Weight
kg
7.7
7.7
7.7
Colour
Star White (N9.3)
Star White (N9.3)
Star White (N9.3)
Condensate Drain
mm
φ
16mm
φ
16mm
φ
16mm
Running current (C/H)
A
Power supply
From OUTDOOR
From OUTDOOR
From OUTDOOR
Cable section (Interconnection)
mm²
1.50x 3+EARTH/-
1.50x 3+EARTH/-
1.50x 3+EARTH/-
Piping diameter (Liq / Gas)
Inch
1/4" / 3/8"
1/4" / 3/8"
1/4" / 3/8"
Drain diameter (ext)
mm
φ
16
φ
16
φ
16
Remote control (standard/optional)
RAR-7PE1/
SPX-RCDB
RAR-7PE1/
SPX-RCDB
RAR-7PE1/
SPX-RCDB
Filter
ACL Filter
Active Carbon
Active Carbon
Active Carbon
ACL part name
SPX-CFH25
SPX-CFH25
SPX-CFH25
Pre-filter (Standard / Optional)
Washable /
Stainless(
SPX-SPF8
)
Washable /
Stainless(
SPX-SPF8
)
Washable /
Stainless(
SPX-SPF8
)
NOTE:
1. Capacity and seasonal performance data (SEER
/SCOP) are based on EN14511 and EN14825. The
nominal heating and cooling capacity is the combined
capacity of the HITACHI Split system ( Outdoor
Unit).
2. The Sound Pressure Level is based on the following
conditions:
-
0.8 meter beneath indoor height center
-
1 meter from Discharge grille
The above data was measured in an anechoic
chamber. Please take into consideration reflected
sound of your specific site
Operation Conditions
Cooling
Heating
Indoor Air Inlet Temperature
dB
27.0 °C
20.0 °C
WB
19.0 °C
Outdoor Air Inlet Temperature
dB
35.0 °C
7.0 °C
WB
6.0 °C
Piping Length
: 5.0 meters;
Piping Lift
: 0 meter
dB
: Dry Bulb;
WB
: Wet Bulb
Summary of Contents for MULTIZONE RAM-40NE2F
Page 11: ...DIMENSIONAL DATA 2 3 2 2 MULTIZONE OUTDOOR UNITS 2 2 1 2 ROOMS MULTIZONE RAM 40NE2F ...
Page 12: ...DIMENSIONAL DATA 2 4 2 2 2 2 ROOMS MULTIZONE RAM 53NE2F Unit mm ...
Page 13: ...DIMENSIONAL DATA 2 5 2 2 3 3 ROOMS MULTIZONE RAM 53NE3F Unit mm ...
Page 63: ...WIRING DIAGRAM 7 2 7 1 MULTIZONE 7 1 1 RAK 15QEF RAK 18REF RAK 25REF RAK 35REF RAK 50REF ...
Page 64: ...WIRING DIAGRAM 7 3 7 1 2 RAM 40NE2F RAM 53NE2F ...
Page 65: ...WIRING DIAGRAM 7 4 7 1 3 RAM 53NE3F ...
Page 68: ...REFRIGERANT CYCLE CYC8 3L 8 1 2 WALL TYPE RAK 50REF ...
Page 69: ...REFRIGERANT CYCLE 8 4 8 2 MULTIZONE OUTDOOR UNITS 8 2 1 2 ROOMS MULTIZONE RAM 40NE2F ...
Page 70: ...REFRIGERANT CYCLE CYC8 5L 8 2 3 2 ROOMS MULTIZONE RAM 53NE2F φ12 7 ...
Page 71: ...REFRIGERANT CYCLE 8 6 8 2 4 3 ROOMS MULTIZONE RAM 53NE3F ...
Page 74: ...CONTROL AND FUNCTION 9 3 9 2 SHIFT VALUE ...
Page 75: ...9 4 CONTROL AND FUNCTION 9 3 DISPLAY OPERATION MODE SETTING ...
Page 76: ...CONTROL AND FUNCTION 9 5 9 4 HOW TO CHANGE THE INTERMITTENT FAN CONTROL SETTING ...
Page 77: ...9 6 CONTROL AND FUNCTION 9 5 HOW TO CHANGE THE FAN SPEED IN COOLING MODE DURING THERMO OFF ...
Page 78: ...CONTROL AND FUNCTION 9 7 9 6 SETTING THE PREVENTION OF MUTUAL INTERFERENCE ...