Chapter 13 Option
13 - 19
“C” Function
Run
Mode
Edit
Defaults
Func.
Code
Name
Description
Initial data
standard
200/400
Initial data
CHN
200/400
Initial data
EU
200/400
Units
C001
Input [1] function
Select input terminal [1] function, 34
options (see next section)
00
[FW]
←
←
C002
Input [2] function
Select input terminal [2] function, 34
options (see next section)
01
[RV]
←
←
C003
Input [3] function
Select input terminal [3] function, 34
options (see next section)
02
[CF1]
←
←
C004
Input [4] function
Select input terminal [4] function, 34
options (see next section)
03
[CF2]
←
←
C005
Input [5] function
Select input terminal [5] function, 34
options (see next section)
18
[RS]
←
←
C011
Input [1] active
state
Select logic conversion, two option
codes:
00
normally open [NO]
01
normally closed [NC]
00
←
←
C012
Input [2] active
state
00
←
←
C013
Input [3] active
state
00
←
←
C014
Input [4] active
state
00
←
←
C015
Input [5] active
state
00
←
←
C021
Output [11]
function
27 programmable functions available for
logic (discrete) outputs
(see next section)
01
[FA1]
←
←
C026
Alarm relay
function
27 programmable functions available for
logic (discrete) outputs
(see next section)
05
[AL]
←
←
C027
[FM] terminal
selection
(Pulse/PWM
output)
9 programmable functions:
00
Output frequency (PWM)
01
Output current (PWM)
03
Output frequency (Pulse train)
04
Output voltage (PWM)
05
Input power (PWM)
06
Electronic thermal load ratio (PWM)
07
LAD frequency (PWM)
08
Output current (Pulse train)
10
Heat sink temperature (PWM)
07
←
←
C030
Digital current
monitor reference
value
Current with digital current monitor
output at 1,440Hz
Range is 20%~200% of rated current
Rated
current
←
←
A
C031
Output [11] active
state
Select logic conversion, two option
codes:
00
normally open [NO]
01
normally closed [NC]
00
←
←
C036
Alarm relay active
state
01
←
←
C038
Output mode of
low current
detection
Two option codes:
00
During acceleration, deceleration
and constant speed
01
During constant speed only
01
←
←
C039
Low current
detection level
Set the level of low load detection, range
is 0.00 to 2.00*inverter rated current
Rated
current
←
←
A
C040
Output mode of
overload warning
Two option codes:
00
During accel., decel. and constant
speed
01
During constant speed only
01
←
←
C041
Overload warning
level
Sets the overload warning signal level
between 0% and 200% (from 0 to two
time the rated current of the inverter)
Rated
current
x 1.15
←
←
A
Summary of Contents for NES1-002LB
Page 9: ......
Page 21: ......
Page 25: ......
Page 28: ...Chapter 3 Exterior Views 3 3 ...
Page 30: ......
Page 35: ......
Page 53: ......
Page 75: ......
Page 154: ......
Page 196: ......
Page 203: ...Chapter 10 Troubleshooting This chapter describes the troubleshooting methods ...
Page 204: ......
Page 211: ......
Page 219: ......
Page 229: ......
Page 289: ...Appendix Appendix A Appendix A 1 ...
Page 290: ......
Page 292: ...Appendix Appendix 2 ...