2-18
Chapter 2
Installation and Wiring
■
Recommended terminals for wiring
• The following ferrule terminals are recommended for
signal cable for easy wiring and improved reliability of
connectivity.
Ferrule terminal with sleeves
*) Manufacturer: Phoenix Contact
■
Wiring procedure
1. Push the gray part on the control circuit terminal block
into the socket with a slotted screwdriver (with a wide
of 2.5mm or less). (Insertion hole will open)
2. Insert the wire or ferrule terminal into the wire
insertion hole (round) while pressing the gray part with
a slotted screwdriver.
3. The wire is connected when release the screw driver.
Crimping tool: CRIMPFOX UD 6-4 or CRIMPFOX ZA 3
• Even for pulling out the wire from the socket, press the
gray part with a slotted screwdriver (the insertion hole
will be opened while pressing).
Power cable size
mm
2
(AWG)
Ferrule terminal
model
*
L1 [mm]
L2 [mm]
φ
d [mm]
φ
D [mm]
0.25 (24)
AI 0,25-8YE
8
12.5
0.8
2.0
0.34 (22)
AI 0,34-8TQ
8
12.5
0.8
2.0
0.5 (20)
AI 0,5-8WH
8
14
1.1
2.5
0.75 (18)
AI 0,75-8GY
8
14
1.3
2.8
Push the gray part into
the socket with a slotted
screwdriver
Insert the wire
The wire is connected
when release the screw
driver
2.5mm