4-17
Chapter 4
For parameter configuration
[AC-30]
~
[AC-88]
Setting for two-stage Acc/Decel time
Code/Name
Range (unit) Unit value
AC-30
Acc. time for Multispeed-1
0.00
~
3600.00(s)
30.00
AC-32
Decel. time for Multispeed-1
30.00
AC-34
Acc. time for Multispeed-2
30.00
AC-36
Decel. time for Multispeed-2
30.00
AC-38
Acc. time for Multispeed-3
30.00
AC-40
Decel. time for Multispeed-3
30.00
AC-42
Acc. time for Multispeed-4
30.00
AC-44
Decel. time for Multispeed-4
30.00
AC-46
Acc. time for Multispeed-5
30.00
AC-48
Decel. time for Multispeed-5
30.00
AC-50
Acc. time for Multispeed-6
30.00
AC-52
Decel. time for Multispeed-6
30.00
AC-54
Acc. time for Multispeed-7
30.00
AC-56
Decel. time for Multispeed-7
30.00
AC-58
Acc. time for Multispeed-8
30.00
AC-60
Decel. time for Multispeed-8
30.00
AC-62
Acc. time for Multispeed-9
30.00
AC-64
Decel. time for Multispeed-9
30.00
AC-66
Acc. time for Multispeed-10
30.00
AC-68
Decel. time for Multispeed-10
30.00
AC-70
Acc. time for Multispeed-11
30.00
AC-72
Decel. time for Multispeed-11
30.00
AC-74
Acc. time for Multispeed-12
30.00
AC-76
Decel. time for Multispeed-12
30.00
AC-78
Acc. time for Multispeed-13
30.00
AC-80
Decel. time for Multispeed-13
30.00
AC-82
Acc. time for Multispeed-14
30.00
AC-84
Decel. time for Multispeed-14
30.00
AC-86
Acc. time for Multispeed-15
30.00
AC-88
Decel. time for Multispeed-15
30.00
・
Individual Acc/Decel times can be set for multispeed
functions[Ab-11]
~
[Ab-25].
[AC215]
~
[Ad-15]
2nd motor
When Intelligent Input terminal 024[SET] is enabled.
Code/Name
Range (unit) Initial value
AC215
Select method to switch to
Acc2/Decel2 Profile, 2nd-motor
Same as AC115
AC216
Acc1 to Acc2 frequency
transition point, 2nd-motor
Same as AC116
AC217
Decel1 to Decel2 frequency
transition point, 2nd-motor
Same as AC117
AC220
Acceleration time
1, 2nd-motor
Same as AC120
AC222
Deceleration time 1, 2nd-motor
Same as AC122
AC224
Acceleration time 2, 2nd-motor
Same as AC124
AC226
Deceleration time 2, 2nd-motor
Same as AC126
Torque control function setting
Code/Name
Range (unit)
Initial
value
Ad-01
Torque reference input
source selection
01
~
06/09
~
18 *1)
07
Ad-02
Torque reference value
setting
-500.0
~
500.0(%)
0.0
Ad-03
Polarity selection for
torque reference
00(According
to
sign)/
01(Depend on the
operation direction)
00
Ad-04
Switching time of speed
control to torque control
0
~
1000(ms)
0
・
Operations settings of torque control.
For more information, refer to the User’s guide.
Torque bias setting
Code/Name
Range (unit)
Initial
value
Ad-11
Torque bias input
source selection
01
~
06/09
~
18 *1)
07
Ad-12
Torque bias value setting
-500.0
~
500.0(%)
0.0
Ad-13
Polarity selection for torque bias
00(According
to
sign)/
01(Depend on the
operation direction)
00
Ad-14
Terminal [TBS] active
00(Disable)/
01(Enable)
00
・
For setting the torque bias.
For more information, refer to the User’s guide.
Speed limitation for torque control
Code/Name
Range (unit)
Initial value
Ad-40
Input selection for
speed limit at torque control
01
~
13 *1)
07
Ad-41
Speed limit at torque
control (at Forward rotation)
0.00
~
590.00(Hz)
0.00
Ad-42
Speed limit at torque
control (at Reverse rotation)
0.00
・
In middle of the torque control the speed limit can be
set.
For more information, refer to the User’s guide.
*1)00(Disable)/01(Ai1 terminal)/02(Ai2 terminal)/03(Ai3 terminal)/
07(Parameter)/08(RS485)/13(Pulse train input:main)/ 14(Program
function)/15(PID calc.)
Speed 2 [Ab-12]
Speed 3 [Ab-13],
Speed 4 [Ab-14]
Speed 1 [Ab-11]
Multispeed
FW
Speed 1 Speed
2
Speed
3
Speed
2
Speed
4
Speed
3
Speed
1
Speed 4
Acc/decel time
Acc. 1
[AC-30]
Acc. 2
[AC-34]
Acc. 3
[AC-38]
Decel. 3
[AC-40]
Acc. 4
[AC-42]
Same
as
before
Decel. 3
[AC-40]
Acc. 4
[AC-42]
Decel. 4
[AC-44]
This will be effective only for Acc./Dec.
time if the set frequency is the same.