INSTALLATION OF REMOTE CONTROL SWITCH <PC-2H2>

6

2.

 

CHECK FUNCTION USING THE REMOTE CONTROL

2.1.

 

ALARM CODES

Indication

Trouble

Possible Causes

Action

Remote cable broken

Contact Failure in Remote control cable

Locate the cause and
repair.

RUN lamp Flashes for
2 Seconds

Failure in Transmission
Between Indoor Unit and
Remote Control Switch

IC or Microcomputer defective

Check by remote
control self-checking
function

RUN lamp flashes 5 times
(5 seconds) with unit number
and alarm code displayed

Failure

(see Code)

Alarm Codes

Code

Cause

Model

01

Safety Device of the Indoor Unit is tripped (internal Thermostat, *Float Switch)

Heat Pump & Twin

Safety Device of the Outdoor Unit is tripped (High pressure switch, Internal Thermostat
for Outdoor Fan Motor and Overcurrent Relay)

Heat Pump & Twin

02

Safety Device of the Outdoor Unit is tripped (Overcurrent Relay, Compressor Chamber
Thermostat, High Pressure Switch and Internal Thermostat for Outdoor and Indoor Fan
Motor)

Cooling Only Models

03

Transmission Abnormality between Indoor Unit and Outdoor Unit

Heat Pump & Twin

05

Picking up phase Abnormality

Heat Pump & Twin

08

Abnormality High Temperature on the Top of Compressor

Heat Pump & Twin

11

Thermistor Abnormality for inlet Air Temperature

All Models

12

Thermistor Abnormality for outlet Air Temperature

Heat Pump & Twin

13

Thermistor Abnormality for Freezing Temperature

All Models

20

Thermistor Abnormality for Compressor Top Temperature

Heat Pump & Twin

22

Thermistor Abnormality for Outdoor Air Temperature

Heat Pump & Twin

24

Thermistor Abnormality for Outdoor Evaporating Temperature (defrosting)

Heat Pump & Twin

25

Thermistor Abnormality for Condensing Temperature

Heat Pump & Twin

32

Transmision Abnormality between Master and Slave

Only Twin system

38

 Abnormality in the Picking up Circuit protection All Models

41

Excessive Overload during Cooling Operation

Heat Pump & Twin

42

Excessive Overload during Heating Operation

Heat Pump & Twin

(* Only for RCI models & RPI with Drain Kit)

NOTES:

 If an 02 cooling only models/05 heat pump models alarm
code appers when the unit is operated for the first time,
please check that incoming phases are correctly connected.
Inverse 2 of the 3 phases and retry.

Indication of unit number in remote control switch master or
single unit.

Unit 0

Unit 1

Unit 2

Unit 3

Unit 4

Unit 5

Unit 6

Unit 7

) ) )  )! )" )# )$ )%

Indication of unit number in remote control switch slave or
single unit.

Unit 8

Unit 9

Unit 10 Unit 11 Unit 12 Unit 13 Unit 14 Unit 15

)& )' )) )> )+ )@ )- ).

Example:

)!

Unit Nº 3

 

Alarm Code of
"outdoor Unit
Protection Activated"

Summary of Contents for PC-2H2

Page 1: ...onsultazioni Leia e compreenda este manual antes de operar este ar condicionado Guarde este manual para futura referencia De bor laese og forsta denne vejledning for de tager dette dlimaanlaeg i brug Opbervar vejledningen til senere reference Lees deze hadleiding aandachtig door alvorens de airconditioning in gebruik te nemen Läs och första denna manual innan Du sätter igang luftkonditioneraren Fö...

Page 2: ......

Page 3: ...run any cable for transmission and signal along the power line 220 240V 380 415V DO NOT run any cable for transmission and signal along other cables for transmission and signal If the cables are required to be run along keep a distance more than 30 cm between each cables or insert the cables for each transmission system into the metal conduit tube and ground one end of the conduit tube n Location ...

Page 4: ...f the holding bracket push and turn the screwdriver and remove the controller from the holding bracket as shown in the figure below Fig 2 Installation Procedure Fig 3 Installation Procedure 2 Attach the controller to the holding bracket as follows A In case of exposing Remote Control Cable É Fix the holding bracket onto the wall as shown below Fig 4 Attach the controller Ê Make the hole for drawin...

Page 5: ...nting work is finished Fig 10 Mounting procedures CAUTION Pay attention so that the cable may not be slack If the cable is slack as shown in the above figure the cable cord especially the naked part may be clamped at the hole and it may cause a faulty operation 1 4 WIRING SYSTEM FOR REMOTE CONTROL SWITCH PC 2H2 1 4 1 LENGTH OF WIRE CABLE FOR REMOTE CONTROL SWITCH Length of the standard wire cable ...

Page 6: ...wires B After checking the color of the wires connect each wire of the same color by soldering C Insulate the soldered parts and the wires with insulation tape D The maximum total cable length of the remote control switch cable and the bridge cable s is 200 meters 0 3mm2 wire or 500 meters 0 75mm2 wire 3 Separate the cable more than approximately 30cm from any wires which are utilized for wires hi...

Page 7: ... Bridge Cable 9 Contact of Connectors of Bridge Cable Ë Back to É after checking Ì Select TEST RUN MODE by depressing MODE Switch COOL OR HEAT Í Depress RUN STOP switch a The TEST RUN operation will be started The TEST RUN operation will be finished after 2 hours unit operation or by depressing the RUN STOP switch again b IF the unit do not start or the operation lamp on the remote control switch ...

Page 8: ...pressor Heat Pump Twin 11 Thermistor Abnormality for inlet Air Temperature All Models 12 Thermistor Abnormality for outlet Air Temperature Heat Pump Twin 13 Thermistor Abnormality for Freezing Temperature All Models 20 Thermistor Abnormality for Compressor Top Temperature Heat Pump Twin 22 Thermistor Abnormality for Outdoor Air Temperature Heat Pump Twin 24 Thermistor Abnormality for Outdoor Evapo...

Page 9: ...etting temperature is turned OFF b At the condition of the above item a press the TEMP switch or the TEMP switch of the remote control switch and the indoor unit for which the optional function is to be set can be changed NOTES The indoor unit can be selected among the indoor units connected to the remote control switch In case that both the indications of the address and the refrigerant cycle num...

Page 10: ...0 01 Not Available Available b4 Change of Filter Cleaning Time 00 01 02 03 04 Standard 100 hours 1200 hours 2500 hours Not Indication b5 Fixing of Operation Mode 00 01 Not Available Available b6 Fixing of Setting Temperature 00 01 Not Available Available b7 Fixing of Operation as Exclusive Cooling Unit 00 01 Not Available Available b8 Automatic COOL HEAT 00 01 Not Available Available b9 Fixing of ...

Page 11: ......

Page 12: ...PMML0041B 12 01 Printed in Spain ...

Reviews: