(1) Turn the outdoor unit power ON.
■ Apply power to the outdoor unit(s) at least 12 hours prior to operation of the system for preheating of the
compresssor oil.
■ Do not turn the power OFF during this period.
(2) Turn the PSC-A128WEB3 power ON.
■ Concerning the connection and installation of this unit, refer to the installation and operation manual.
■ When it is the first time the power is turned ON, uninstall all the central controllers connected,
and after checking the connection, connect them back.
(3) Turn the power ON on the computer.
■ Follow the instructions in each operation manual
concerning the power supply order for the computer.
(4) Modify the IP Address of the computer if necessary.
The initial setting of the PSC-A128WEB3 IP address is [192.168.0.3].
The same IP address cannot be duplicated on the same
network.
1 Power Supply
Preparation for Setup
■ Windows
®
7
1. Select [Start].
2. Select [Control Panel].
3. Change [View by] on the top right in [Small Icon].
4. Select [Network and Sharing Center].
5. Select [Change adapter setting].
6. Right-click [Local Area Connection] and select [Properties].
7. Select [Properties] of [Internet Protocol Version 4 (TCP/IPv4)].
8. Modify the value within the dashed line indicated in the chart on the right and Click on [OK].
■ Windows
®
8
1. Indicate the menu on the right side of the screen.
2. Select [Setting] .
3. Select [Control Panel].
4. Change [View by] on the top right in [Small Icons].
5. Select [Network and Sharing Center].
6. Select [Change adapter setting].
7. Right-click [Local Area Connection] and select [Properties].
8. Select [Properties] of [Internet Protocol Version 4 (TCP/IPv4)].
9. Modify the value within the dashed line indicated in the chart on the right and Click on [OK].
NOTICE:
● The menu for Windows
®
8 will be indicated when moving the mouse cursor on the top right of the
screen.
● Consult with the network administrator for the correct static IP, subnet mask and default gateway that
should be configured for the PSC-A128WEB3.
NOTE:
● When using a Proxy server, this unit may not be able to communicate. Remove the check marks from