P5416904
45
NOTICE:
Registered Data
The following correspond to the [registered data] indicated when executing a Check connection.
1. Setting content of the Unit Register screen.
2. Setting content of the RC Group Register screen.
3. Setting content of the Group Register screen.
4. Setting content of the Block Register screen.
However, for a result of executing the Check connection, only the registered data connection not recognized
is deleted.
Also, for a result of executing the Check connection, the data which is newly recognized is treated the same
as when the Check connection is executed for the first time.
In addition, concerning the following data, even if executing the Check connection, the setting content is not
changing.
● Setting content of the Schedule screen.
● Alarm History.
● Setting content other than setting screen 1 to 4.
NOTE:
In that case, even outside the first Test Run, the Check connection is always required.
1. If the RC of the Indoor unit or cross wiring is installed or removed.
2. If the expansion, removal, model modification of the AC or Central controller used in combination is
generated.
3. In any case, when using as it is, the model of AC already registered, the Group Register content or the
Block Register content, select and execute the Check connection. (The Check connection is performed
using registered data.)
4. If the Check connection concerning the control of the Indoor unit is performed.