64
P5416904
< Alarm Code Table >
Alarm Code
Contents
Active to Take
00
~
FF
(Excludes 60, 61, 64
and 65)
Alarm displayed on air
conditioning unit
Refer to the installation & maintenance manual and
the operation manual for each air conditioning unit.
60
Central controller - Outdoor unit
communication error
(when more than 1 unit(s)
operating)
A communication error has occurred on the H-LINK
between the adapter for this system and the outdoor unit.
Check if the H-LINK is properly connected.
61
Indoor unit - Central controller
communication error
(when no indoor units are
operating)
A communication error has occurred on the H-LINK
between the adapter for this system and the indoor unit.
Check if the H-LINK is properly connected.
64
Central controller - Outdoor unit
communication error
(when all Indoor units are not
operating)
A communication error has occurred on the H-LINK
between the adapter for this system and the outdoor unit.
Check if the H-LINK is properly connected.
65
Indoor unit - Central controller
communication error
(when an indoor unit is not
operating)
A communication error has occurred on the H-LINK
between the adapter for this system and the outdoor unit.
Check if the H-LINK is properly connected.