No.
Event
Items to be checked
Action
16 What is indicated
on the Monitor does
not match what is
indicated on the Local
Remote.
Check if control is done from
both the system and the Local
Remote.
In that case, it may take up to 7 minutes for the
status to match.
17 The panel is not
displayed.
Check if the connection check is
correctly completed.
Go to [Settings] - [Unit register] and check the
connection status of the unit.
Check that there is no error
between the Computer and this
system connection.
Check if the LAN cable is wired correctly and if
the HUB and this system power is turned ON.
18 The display units have
changed.
Is the group to be displayed
selected?
If the group to be displayed is selected, the
display unit will automatically switch to unit.
Check if the alarm is ON.
If the alarm is ON, the display object will
automatically be in All and the display unit will
change into Group.
19 The selected display
unit has changed.
Check if the alarm is ON.
If the alarm is ON, the display object will
automatically be in All and the display unit will
change into Group.
Check the Alarm History.
20
Even modifying the
Operation Mode, the
color of the panel
does not change and
will stay in green when
the AC is running.
Check if the color for operation
mode is modified in [Settings]-
[Display/Sound].
Check the operation mode color in [Settings] -
[Display/Sound].
21 There is a wide
temperature
discrepancy between
what is displayed
and the actual
temperature.
Is the Power Saving function of
the Local Remote activated ?
In case the Power Saving function of the Local
Remote is activated, the temperature displayed
may widely differ from the actual temperature.
22 Schedule is not
executed.
Was the Schedule disabled for
one day?
Open the control panel of the unit in the monitor
screen and deselect [1day OFF].
After setting the Schedule, is the
[Done] button selected?
Click on [Done].
Is the [Done] button blinking?
Click on [Done]. The button will stop blinking
after modification is effected.
Is the schedule registered in
"Group"?
Schedule will be applied by each Group.
Check if each Group is set to execute that
Schedule.
Is any specific Schedule
registered?
Specific schedule will be performed even when
the daily schedule is set, if the current day is
registered as a specific schedule. Check the
content of the specific schedule.