6-40
●
Transmission Sequences
6.4.10 Calendar Conditions Transmission Procedure
Text
(1) Offset
ESC
Header 76H Item No. Type
thousands hundreds tens position unit position
position position
Code of type
Offset Year
Month Day Hour Minute
ASCII 30 31 32 33 34
Offset setting range
ASCII is hexadecimal
"-" (2DH) when setting negative
offset to hour, minute.
Offset setting range
00 to 99
00 to 99
0000 to 1999
-23 to 99
-59 to 99
Setting item
Year
Month
Day
Hour
Minute
(2) Zero-suppression
Code of type
Zero-suppression Year
Month Day Hour Minute
ASCII 30 31 32 33 34
ASCII is hexadecimal
Disable or Enable (0: Disable; 1: Enable)
ESC
Header 77H Item No. Type Disable
or Enable
6.4.11 Online/Offline Transmission Procedure
Text
(1) Change to online
(2) Change to offline
ESC
Header 79H
ESC
Header 7AH
¡
In the following cases, Online/Offline transmission cannot be performed.
If it is attempted, NAK code will be the reply:
"Apply" key is displayed while inputting set value.
In the "Communication environment setup" screen, "Off fixed" is selected for
"State at power-up" item.
During input of count conditions.
The confirmation window is open.
The circulation control screen is opened by the maintenance function.
The touch screen setup screen is opened by the auxiliary function.
1
2
3
4
5
6
Summary of Contents for PXR-D
Page 319: ...3S23L1307 3B PXR D E7 HEC ...