– 129 –
Does the transflux fan rotate gently?
(Be sure to turn off the power before checking it.)
Run the product with the remote control unit set to
"cooling, strong wind".
Has the indoor fan motor run for several seconds?
While the fan was turning, did an FG pulse signal
occur between pins
④
and
⑦
of the fan motor
connector (CN2)?
(These signals should normally occur only while the
fan is rotating.)
Does a 15 V voltage occur between pins
④
and
⑤
of
the fan motor connector (CN2)?
11. Timer lamp blinking: blinking 10 times
[Situation] The timer lamp blinks 10 times and the product will not run.
[Estimated failure locations]
・
Loose connector or wire break in the indoor fan motor
・
Indoor fan motor mechanically locked
・
Indoor fan motor
・
Indoor fan motor drive circuit
[Diagnosis flow]
Initiating troubleshooting
No
No
No
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Remove the cause of the mechanical lock.
Is the indoor fan motor connector (CN2) securely
inserted? Is it free of wire breaks?
Correct the connector and wiring.
For 2 to 3 seconds after startup by remote control,
did a voltage of about 3-6 V occur between pins
④
and
⑥
of the fan motor connector (CN2)?
Replace the "indoor electrical parts".
Replace the "indoor fan motor".
Replace the "indoor electrical parts".
Is there a factor that mechanically hampers the rotation?
・
The transflux fan is hitting and rubbing against something.
・
There are deposits of viscous dust.
Replace the "indoor fan motor".
Summary of Contents for RAC-10SH3
Page 57: ... 55 MODEL RAC 18SH3 Unit mm 580 5 600 345 299 19 5 ...
Page 60: ... 8 5 WIRING DIAGRAM MODEL RAS 10SH3 3 H S 4 1 S A R 3 H S 8 1 S A R INDOOR UNIT ...
Page 62: ... 0 6 MODEL RAC 18SH3 OUTDOOR UNIT WHT YEL RED INDOOR UNIT ...
Page 64: ... 2 6 3 H S 8 1 S A R 3 H S 4 1 S A R 3 H S 0 1 S A R L E D O M ...
Page 150: ... 8 4 1 MODEL RAC 18SH3 ...
Page 153: ...HHAW NO 0060E RAS 10SH3 RAC 10SH3 RAS 14SH3 RAC 10SH3 RAS 18SH3 RAC 18SH3 ...