The air de
fl
ector control operation shown below is done when the swing switch
is pressed or when the operation mode is changed.
●
The air de
fl
ector control operation shown below is done when the operation
switch is turned off.
Item
3-way
AUTO (Swing)
Speci
fi
cation
Cooling/
dehumidi-
fying
Heating
(When the
operation
switch is
turned off
Automatic
shut opera-
tion)
Air
blowing
direction
control
8
The same as cooling
●
dehumidifying
Other detailed speci
fi
cations
1. When the room temperature starts to
increase within 3 minutes after thermo
OFF in “cooling” and fan speed “AUTO”,
the fan speed changes L
→
M
→
H as
when thermo ON.
2. If “cooling” is selected during “sensor
dehumidi
fi
cation” operation the operation
continues as it is with the thermo ON.
The 3 minutes delay is not started. The
set temperature and fan speed depend
on the remote control signal.
It is same for “cooling” – – – – “sensor
dehumidi
fi
cation”. It is same for “AUTO”
sensor dehumidi
fi
cation cooling “sensor
dehumidi
fi
cation” “cooling”.
3. The filter sign lights after 200 hours
operation of the room fan. The lamp goes
out when the POWER SWITCH set to
OFF and ON again.
4. After the failure mode is started (indicator
lamp
fl
ickering), rapid mode changing
cannot be done.
5. If the operation is made by the nice
temperature reservation during the
sleep operation, the normal operation
continuously occurs, and for the advance
time, the temperature difference between
the set temperature without sleep shift
and “room temperature” is used.
– 45 –
●
Operation starts in advance so that the room temperature reaches
the preset value at the set time.
●
The operation time is obtained as follows depending on the room
temperature when operation starts.
(1) Calculation method of the moved-up time.
Moved-up time (MT) = Moved-up time depending on the temperature
difference (OT) + compensation time (HT).
MT is at least 1 minute if OT is not zero.
Heating
Cooling
(MT)
00 ~ 60 min.
00 ~ 60 min.
(OT)
00 ~ 60 min.
00 ~ 60 min.
(HT)
–60 ~ 60 min.
–60 ~ 60 min.
Obtain OT (moved-up time depending on the temperature difference)
from the table below.
10
“NICE
TEMPERA-
TURE”
reservation
Heating
Cooling
Setting temp. – Room temp. Time (min.) Setting temp. – Room temp. Time (min.)
00 – 01.00
00
00.00 – 02.00
00
01.25 – 03.00
10
02.25 – 05.00
15
03.25 – 07.00
20
05.25 – 08.00
30
07.25 – 10.00
30
08.25 – 11.00
45
10.25 – 13.00
40
11.25 –
60
13.25 – 16.00
50
16.25 – 19.00
60
19.25 – 22.00
60
22.25 –
❈
The preset temperature value shown above does not
include any shift value.
(2) Compensation
1 The “Attained” state is monitored and a “Not attained” check is
done to revise the compensation time (HT).
“Attained” monitor
Continuously monitored during “NICE TEMPERATURE” operation.
(Heating)
When the room temperature < Set value + compensation shift,
it is regarded to be “attained” and 5 minutes are reduced from
the compensation time.
(Cooling)
When the room temperature < Set value + compensation shift,
it’s operated same as above.
“Not attained” check
Performed once when the “NICE TEMPERATURE” timer is completed.
(Heating)
When the room temperature < Set value + compensation shift
1°C, it is regarded to be “Not attained” and 5 minutes are added
to the compensation time.
(Cooling)
When the room temperature > Set value + compensation shift
+1°C, it’s operated same as above.
❈
If the room temperature is 1°C from the set value +
compensation shift, compensation is not done.
Item
ON
temperature
Thermostat operation (Thermostat relay)
power relay (°C)
Differential
(°C)
Low-temperature defrosting
Cooling, sensor
dehumidi
fi
cation
(T1)
RAS-18GH5
16
17.6
24
25.6
33.6
0.33
ON
(°C)
4.0
Reset (°C)
12.0
Table 2 Sensor operation values
Item
RAS-18GH
Automatic
Yes
Heating
Yes
Operation switching
Sensor dehumidi
fi
cation
Yes
Cooling
Yes
Fan
Yes
Temporary switch
Yes (automatic)
Service switch
Cooling
Yes
Nice temperature reservation
Yes
Defrosting
Yes
Sleep circuit
Yes
Heater operation at the time of sensor dehumidi
fi
cation
No
Automatic blowing direction
Yes
Filter sign
Yes
Wireless mode
Heat and Cool wireless
Table 1 Speci
fi
cations
Down
Up
Down
Up
❈
Swing start direction
5
Summary of Contents for RAC-18GH5
Page 32: ... 31 MODEL RAC 18GH5 Note 1 200mm or more servicing space is required above the outdoor unit ...
Page 36: ... 35 CIRCUIT DIAGRAM Remote Control ...
Page 38: ... 39 BLOCK DIAGRAM MODEL RAS 18GH5 RAC 18GH5 ...
Page 42: ... 47 REFRIGERATING CYCLE DIAGRAM MODEL RAS 18GH5 RAC 18GH5 ...
Page 61: ...PM NO 0479E Printed in Malaysia RAS 18GH5 RAC 18GH5 ...