4. Failure phenomenon: The fan motor will not stop.
>
Situation
@
I have conducted the stop operation on the product by remote control, but the indoor fan motor will not stop.
>
Estimated failure locations
@
·
Indoor fan motor
·
Fan motor drive circuit
>
Diagnosis flow
@
Initiating troubleshooting
Yes
Replace the "indoor fan motor".
No
Replace the "indoor electrical unit".
Run the product by remote control and then stop it.
(Reproduce the failure phenomenon.)
Is the voltage between pins
connector (CN10) below 1.1 V? (Take measurements
while the failure phenomenon is present.)
2 and 4 of the fan motor
92