background image

– 

EN

GL

IS

H

HEATING 

OPERATION

 

Use 

the 

device 

for 

heating 

when 

the 

outdoor 

temperature 

is 

under 

21°C.

 

When 

it 

is 

too 

warm 

(over 

21°C), 

the 

heating 

function 

may 

not 

work 

in 

order 

to 

protect 

the 

device.

 

In 

order 

to 

maintain 

reliability 

of 

the 

device, 

please 

use 

this 

device 

when 

outdoor 

temperature 

is 

above 

–15°C.

Press 

the 

MODE 

selector 

button 

so 

that 

the 

display 

indicates 

   

  

  

 (HEAT).

Set 

the 

desired 

FAN 

SPEED 

with 

the 

  

 (FAN 

SPEED) 

button 

(the 

display 

indicates 

the 

setting).

 

 

 

 

 (AUTO) 

  

  

 

(HIGH) 

  

  

(MED) 

 

 

 (SILENT) 

  

  

 (LOW) 

S

e

th

e

 d

e

s

ir

e

d

 r

o

o

m

 t

e

m

p

e

ra

tu

re

 w

ith

 t

h

e

 T

E

M

P

E

R

A

T

U

R

E

 b

u

tt

o

n

(the 

display 

indicates 

the 

setting).

The 

temperature 

setting 

and 

the 

actual 

room 

temperature 

may 

vary 

depending 

on 

conditions.

Temperature 

range 

can 

be 

set 

between 

16°C 

and 

32°C.

P

re

s

s

 t

h

e

 

 (

S

T

A

R

T

/S

T

O

P

b

u

tt

o

n

H

e

a

ti

n

g

 o

p

e

ra

ti

o

n

 s

ta

rt

s

 w

it

h

 

beep. 

Press 

the 

button 

again 

to 

stop 

operation.

 

As 

the 

settings 

are 

stored 

in 

the 

memory 

of 

the 

remote 

controller, 

you 

only 

have 

to 

press 

the 

 (START/STOP) 

button 

next 

time.

 

During 

AUTO 

fan, 

the 

fan 

speed 

automatically 

changes 

as 

below:

  

 

● 

W

h

e

n

 t

h

e

 d

iff

e

re

n

c

e

 b

e

tw

e

e

n

 r

o

o

m

 t

e

m

p

e

ra

tu

re

 a

n

d

 s

e

tt

in

g

 t

e

m

p

e

ra

tu

re 

is 

large, 

fan 

starts 

to 

run 

at 

HI 

speed.

 

● 

After 

room 

temperature 

reaches 

the 

preset 

temperature, 

fan 

speed 

will 

be 

changed 

to 

lower 

speed 

to 

obtain 

optimum 

room 

temperature 

condition 

for 

natural 

healthy 

heating.

START

STOP

Defrosting 

will 

be 

performed 

about 

once 

an 

hour 

when 

frost 

forms 

on 

the 

heat 

exchange 

of 

the 

outdoor 

unit, 

for 

5~10 

minutes 

each 

time.

During 

defrosting 

operation, 

the 

operation 

lamp 

blinks 

in 

cycle 

of 

seconds 

on 

and 

0.5 

second 

off.

The 

maximum 

time 

for 

defrosting 

is 

20 

minutes.

However, 

if 

the 

indoor 

unit 

is 

connected 

to 

multi 

type 

outdoor 

unit, 

the 

maximum 

time 

for 

defrosting 

is 

15 

minutes.

(If 

the 

piping 

length 

used 

is 

longer 

than 

usual, 

frost 

is 

likely 

to 

form.)

1

2

3

Defrosting

– 

DEHUMIDIFYING 

OPERATION

 

Dehumidifying 

Function

●  

When 

the 

room 

temperature 

is 

higher 

than 

the 

temperature 

setting: 

The 

device 

will 

dehumidify 

the 

room, 

reducing the room temperature to the preset level.

 

When 

the 

room 

temperature 

is 

lower 

than 

the 

temperature 

setting: 

Dehumidifying 

will 

be 

performed 

at 

the 

temperature setting slightly lower than the current room temperature, regardless of the temperature setting. 

●  

The 

preset 

room 

temperature 

may 

not 

be 

reached 

depending 

on 

the 

number 

of 

people 

present 

in 

the 

room 

  

or other room conditions.

Set the desired room temperature with the ROOM 

TEMPERATURE setting buttons (the display indicates the 

setting).

The 

range 

of 

20-26˚C 

is 

recommended 

as 

the 

room temperature for dehumidifying.

T

e

m

p

e

ra

tu

re

 

ra

n

g

e

 

c

a

n

 

b

e

 

s

e

b

e

tw

e

e

n

 

1

6

°C 

and 

32°C.

Press 

the 

 

(START/STOP) 

button. 

Dehumidifying 

operation 

starts with a beep. Press the button again to stop operation.

■  

As the settings are stored in the memory of the remote controller, you 

only have to press the 

 (START/STOP) button next time.

START

STOP

Press  the  MODE  selector button  so  that  the  display  

indicates  

 (DEHUMIDIFY).

The fan speed is set at LOW.

Press 

 (FAN 

SPEED) 

button 

to 

select 

SILENT 

or 

LOW 

fan 

speed.

Use the device for dehumidifying when the room temperature is over 16°C.

When it is under 15°C, the dehumidifying function will not work.

1

2

- 12 -

Summary of Contents for RAC-25WXD

Page 1: ...0 10 920 3 070 14 330 3 74 3 57 3 67 3 51 14 330 3 070 16 380 2 92 2 79 2 50 0 90 3 10 8 530 3 070 10 580 6 36 6 09 3 50 0 90 4 00 5 00 1 90 5 20 11 940 3 070 13 650 17 060 6 480 17 740 20 470 7 510 24 910 6 44 6 16 1 415 500 2 700 4 00 0 90 4 80 5 80 2 20 7 00 XD XD XD XD XD XD RAK 35RXD RAK 25RXD RAK 18QXD RAK 50RXD 295 210 11 792 65 600 299 27 5 37 5 900 295 210 11 800 63 736 350 35 5 51 RAK 35...

Page 2: ... DANGER 2 ...

Page 3: ... rejected goods should be handled in the same way 2 When any part is handled uncovered in counting packing and the like the handling person must always use himself as a body earth Make yourself a body earth by passing one M ohm earth resistance through a ring or bracelet 3 Be careful not to touch the parts with your clothing when you hold a part even if a body earth is being taken 4 Be sure to pla...

Page 4: ...rcuits for maintenance inspection or some others be careful not to have the test probes of the measuring instrument short circuit a load circuit or the like Bare copper wire for body earth Metal plate of Al stainless steel etc Working table Resistor 1MΩ 1 2W Earth wire Staple Fig 3 Grounding of the working table soldering iron Grounding wire Screw stop at the screwed part using a rag plate 4 ...

Page 5: ...r missoperation and re start in a moment there is occasion that the cooling and heating operation does not start for 3 minutes it is not abnormal and this is the result of the operation of IC delay circuit This IC delay circuit ensures that there is no danger of blowing fuse or damaging parts even if operation is restarted accidentally 5 This room air conditioner should not be used at the cooling ...

Page 6: ...CESSOR POWER RELAY POWER SWITCH TEMPORARY SWITCH SERVICE SWITCH TRANSFORMER VARISTOR NOISE SUPPRESSOR THERMOSTAT REMOTE CONTROL SWITCH LIQUID CRYSTAL WITHOUT REFRIGERANT BECAUSE COUPLING IS FLARE TYPE PIPES NO NO NO NO NO NO YES NO NO YES IC YES YES RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 30W DC 3 15A REFRIGERANT CHARGING VOLUME Refrigerant R32 YES 325V TVR10471 6 ...

Page 7: ...The indoor piping should be insulated with the enclosed insulation pipe If the insulator is insufficient please use commercial products Be sure to completely seal any gap with putty 2300 mm or more Plug MODEL 45 RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD Maximum pipe length 20m Maximum pipe length 30m Minimum pipe length 3m 50WXD 25 35WXD 7 ...

Page 8: ...ake sure to turn OFF power supply and then set the position of the switch otherwise will cause damage to the Main PCB 1 2kW 1 2kW 1 2kW 1 8kW 1 8kW 1 8kW SWITCH POSITION CAPACITY SELECTION NOTE FACTORY default setting is at 1 8kW capacity This setting is applicable for RAK 18QXD only 8 ...

Page 9: ...r a long time take the batteries out The batteries will last for approximately 1 year However if the remote controller display begins to fade and degradation of reception performance occurs within a year replace both batteries with new size AAA LR03 alkaline The attached batteries are provided for the initial use of the system The usable period of the batteries may be short depending on the manufa...

Page 10: ...may be shorter This unit can be fi xed on a wall using the fi xture provided Before fi xing it make sure the indoor unit can be controlled from the remote controller Handle the remote controller with care Dropping it or getting it wet may compromise its signal transmission capability After new batteries are inserted into the remote controller the unit will initially require approximately 10 second...

Page 11: ...ation will change when the room temperature varies However the mode of operation will not change when indoor unit is connected to multi type outdoor unit VARIOUS FUNCTIONS Auto Restart Control If there is a power failure operation will be automatically restarted when the power is resumed with previous operation mode and airfl ow direction As the operation is not stopped by remote controller If you...

Page 12: ...peration the operation lamp blinks in a cycle of 3 seconds on and 0 5 second off The maximum time for defrosting is 20 minutes However if the indoor unit is connected to multi type outdoor unit the maximum time for defrosting is 15 minutes If the piping length used is longer than usual frost is likely to form 1 2 3 Defrosting 8 DEHUMIDIFYING OPERATION Dehumidifying Function When the room temperatu...

Page 13: ...does not start if the temperature setting is higher than the current room temperature even though the OPERATION lamp lights The cooling function will start as soon as user set the temperature below the current room temperature 10 FAN OPERATION AUTO SWING OPERATION User can use the device simply as an air circulator VERTICAL SWING HORIZONTAL SWING START STOP 1 2 Press the MODE selector so that the ...

Page 14: ...just before defrost operation when the air conditioner is running in HEATING operation After auto restart POWERFUL operation is cancelled and previous operation shall start For multi model connections POWERFUL operation may not function depending on operation conditions 12 SILENT OPERATION By pressing SILENT button during AUTO HEATING DEHUMIDIFYING COOLING or FAN operation the fan speed will chang...

Page 15: ...temperature automatically and by limiting the maximum power consumption value 14 ECO OPERATION By pressing the ECO button during AUTO HEATING DEHUMIDIFYING or COOLING operation the air conditioner performs the ECO operation 1 To start ECO operation To cancel ECO operation Press ECO button during operation is displayed on the LCD A beep sound is emitted from indoor unit and the ECO lamp on the indo...

Page 16: ...n the unit will operate in previous mode During Leave Home operation fan speed and horizontal air defl ector position cannot be changed By pressing Leave Home button implementation of Weekly Timer or Once Timer is cancelled In case of power supply shut down after autorestart all setting for number of days operation will be reset and unit shall be in continuous operation POWERFUL SILENT and ECO ope...

Page 17: ...ancel Reservation Point the signal window of the remote controller towards the indoor unit and press CANCEL button and ON or OFF set time goes out with a beep and the TIMER lamp on the indoor unit turns off NOTE User can set only one of the OFF timer ON timer or ON OFF timer If WEEKLY TIMER already set by setting the ONCE TIMER ONCE TIMER operation is prioritized When ONCE TIMER operation is compl...

Page 18: ...is possible to select Mode A or Mode B For each mode up to 6 programs can be set per day In total a maximum of 42 programs can be set for a week for each mode If calendar and clock are not set the reservation setting for WEEKLY TIMER cannot be set If calendar and clock are not set correctly WEEKLY TIMER will not operate correctly Reservation for calendar and clock shall be set fi rst before operat...

Page 19: ...e and program number 6 shall have the latest time If the setting time is the same Priority will be given to the latest reservation contents CAUTION If the remote controller is left idle and SEND button is not pressed within 3 minutes after reservations have been made all current reservations will be lost WEEKLY TIMER OPERATION 22 How to select Mode A or Mode B of WEEKLY TIMER setting 1 Press WEEKL...

Page 20: ...lamp lights up If TIMER lamp does not light up Press SEND button again Reservation data will not change if SEND button is not pressed Step 3 Copy and cancel the reservation schedule NOTE If there is no reservation data copying data from one day to another day cannot be done 1 2 3 4 5 6 8 WEEKLY TIMER OPERATION 24 Step 3 Copy and cancel the reservation schedule How to delete WEEKLY TIMER data Delet...

Page 21: ... retrieved from indoor unit To check monthly power consumption Press INFO button Temperature will be displayed for 10 seconds Direct the remote controller towards the receiver of indoor unit within 2 meters in front of indoor unit and press INFO button Wait for 2 seconds for signal transmission Once received the current calendar and clock check whether they are correct or not by pressing CLOCK but...

Page 22: ...will remain This indicates that COOLING and DEHUMIDIFYING mode operation is locked When pressing MODE button or will be displayed Method to unlock COOLING and DEHUMIDIFYING modes including FAN operations Press ECO and SILENT buttons simultaneously for about 5 seconds when the remote controller is OFF All operation mode symbols will appear on the display for about 10 seconds After that operation mo...

Page 23: ...n The deflector s will start to swing up and down is displayed on the LCD Press AUTO SWING VERTICAL button again The deflector s will stop in the current position disappeared from the LCD CAUTION When operating the unit in cooling operation with the air deflector facing down and moving automatically for a long period of time water will be condensed on the air deflector and drips down occasionally ...

Page 24: ...and turn off the circuit breaker Contact your fire may occur if you continue to operate the unit under abnormal situation agent Fault short circuit or in broken copper pipes or faults 3 Ь s t n a l p e h t r o f d a b s i t i s a w o l f r i a e h t r e d n u y l t c e r i d s t n a l p e c a l p t o n o D Ь Do not direct the cool air coming out from the air conditioner panel to face household hea...

Page 25: ...ndition Refer page 5 Horizontal deflector Vertical deflector Air Outlet Remote controller Send out operation signal to the indoor unit So as to operate the whole unit MODEL NAME AND DIMENSIONS MODEL WIDTH mm HEIGHT mm DEPTH mm 900 295 210 ECO Sensor RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 5 NAMES AND FUNCTIONS OF EACH PART If the power stays on and the unit is not operated power is slightly consum...

Page 26: ... 6 7 7 CAUTION Do not splash or direct water to the body of the unit when cleaning it as this may cause short circuit Never use hot water above 40 C benzine gasoline acid thinner or a brush because they will damage the plastic surface and the coating 3 MAINTENANCE AT BEGINNING OF LONG OFF PERIOD Run the unit by setting the operation mode to FAN and the fan speed to HI for about half a day on a fin...

Page 27: ...nit failure or electric shock hazard may result Check to see if the mounting frame has rusted ex cessively or if the outdoor unit has tilted or become unstable It could collapse or fall causing injury AFTER SALES SERVICE AND WARRANTY WHEN ASKING FOR SERVICE CHECK THE FOLLOWING POINTS CONDITION CHECK THE FOLLOWING POINTS s Do the batteries need replacement s Is the polarity of the inserted batterie...

Page 28: ...aporates and steam is emitted Caused as the smells and particles of smoke food cosmetics etc present in room air become attached the unit and blown off into the room again Defrosting is underway as the heating operation is stopped the microcomputer checks frost accumulated in the outdoor unit and instructs the unit to perform automatic defrosting if necessary Shows preheating or defrosting operati...

Page 29: ...AK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD INDOOR UNIT 29 900 295 210 12 7 RAK 50RX More than 50mm More than 2300mm Service space More than 50mm More than 50mm 265 265 370 231 5 231 5 550 668 42 5 193 39 37 100 100 115 180 160 70 530 75 19 3 60 220 4 ...

Page 30: ...S R E W O P T U P T U O DC W 0 3 Control circuit built in M WHT RED YEL 0 6 5V 0V 15V BLU BLK L E D O M THERMOSTAT MODEL IC OPERATION MODE T A E H L O O C ON 15 3 59 54 16 7 62 06 OFF 15 0 59 00 16 7 62 06 ON 23 3 73 94 24 7 76 46 OFF 23 0 73 40 24 7 76 46 ON 31 3 88 34 32 7 90 86 OFF 31 0 87 80 32 7 90 86 TEMPERATURE C F INDICATION 16 INDICATION 24 INDICATION 32 RAK 18QXD RAK 25RXD RAK 35RXD RAK ...

Page 31: ...WIRING DIAGRAM RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 31 ...

Page 32: ...WIRING DIAGRAM OF THE PRINTED WIRING BOARD Remote controller RAR 6N1 SWB SW10 Carbon SW Reset carbon SW 32 ...

Page 33: ...CIRCUIT DIAGRAM MODEL RAK 18QXD 33 ...

Page 34: ...CIRCUIT DIAGRAM MODEL RAK 25RXD RAK 35RXD RAK 50RXD 34 ...

Page 35: ...computer Stepping motor drive circuit Wireless remote controller Wireless receive Reset circuit Control Power circuit Room temperature thermistor Heat exchanger thermistor Oscillator clock circuit Indoor Outdoor interface circuit Indoor DC fan motor send circuit MODEL Infrared sensor Vertical sweep motor 2 ECO Sensor RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD Outdoor unit 1 2 3 35 ...

Page 36: ...ent regardless of the room temperature Runs at ultra Lo when thermo is off Operates at Med regardless of the room temperature Runs at ultra Lo when thermo is off 1 Runs at Hi until room temperature reaches to setting temperature SFTDSC after operation is started 2 Runs at ultra Lo when thermo is off button button button button button button button PDCIN2 PDCOF2 Med Lo Silent 108 Med Lo Silent Sett...

Page 37: ...in 1 900 min 1 900 min 1 53C CMIN_M 900 min 1 900 min 1 900 min 1 900 min 1 900 min 1 53E DMIN_M 900 min 1 900 min 1 900 min 1 900 min 1 900 min 1 53F PKOU_W_M 400 min 1 400 min 1 400 min 1 400 min 1 400 min 1 541 FZZY_GN_M 1 1 1 1 1 543 FZZYTM_M 2min 2min 2min 2min 2min 544 DWNRATEW_M 80 80 80 80 80 545 DWNRATEC_M 60 60 60 60 70 55C SHIFTW_M 0 00 0 00 0 00 0 00 0 00 55D SFTSZW_M 0 00 0 00 0 00 0 ...

Page 38: ...RATEC 60 60 80 SHIFTW 0 00 0 00 3 00 SHIFTC 0 00 0 00 0 00 CLMXTP 30 00 30 00 30 00 TEION 2 00 2 00 2 00 TEIOF 6 00 6 00 6 00 SFTDSW 0 66 0 66 0 66 DFTIM OTP0 43 Minutes 40 Minutes 45 Minutes DFTIM OTP5 43 Minutes 55 Minutes 60 Minutes DFTIM OTP10 43 Minutes 55 Minutes 60 Minutes FCAUT L 0 66 0 66 0 66 FCAUT H 2 00 2 00 2 00 SFTDSC 0 66 0 66 0 66 OFTMPC 1 00 1 00 1 00 DASUPHH 45 00 45 00 39 00 DAS...

Page 39: ... Med fan mode and v change operation mode 3 During Cool Dashed operation thermo off temperature is set temperature with shift value 3 C After thermo off operation continue in Fuzzy control mode 4 Compressor minimum ON time and OFF time is 3 minutes 5 During normal cooling mode compressor maximum rpm CMAX will maintain for 60 minutes if indoor temperature is lower than CLMXTP No time constrain if i...

Page 40: ...tion wil cancel the powerful operation 5 If the sleep timer is set during powerful operation the powerful operation will be canceled 6 When the powerful operation is set the fan speed will be set to HIGH and the compressor s maximum speed will be set to CMAX2 during powerful operation The compressor s lower limit speed is CKYMIN_PW 7 The fan speed increases by FNUPPW_C 8 After the powerful operati...

Page 41: ...The indoor fan is operated in the Lo mode During thermo OFF indoor fan will be OFF for 5 minutes and ON for 1 minute 3 When the operation is started by the themostat turning ON the start of the indoor fan is delayed 32 seconds after the start of compressor operation 4 The compressor is operated forcedly for 3 minutes after operation is started 5 The minimum ON time and OFF time of the compressor a...

Page 42: ...led 6 If the differential the room temperature the temperature setting is the differential 3 after powerful setting the compressor s maximum speed during powerful operation will be set to SDMAX Then the differential reduce the differential 2 33 during powerful operation the compressor s speed will be set to SDRPM If the differential the room temperature the temperature setting is the differential ...

Page 43: ...aximum rpm WMAX will maintain for 120 minutes No time limit constrain if room temperature is 18 or less and outdoor temperature is 2 or less 6 During preheating or defrosting or auto fresh defrosting mode indoor unit operation lamp will blink 7 When heating mode starts it will enter into preheating mode if indoor heat exchanger temperature is less than YNEOF 0 33 8 When fan is set to Med or Lo or ...

Page 44: ...FCLN_WAM_P FCLN_SDF_P CLNCMP Silent button WSZMAX CSZMAX Compresson speed Indoor fan Outdoor fan 8 WUD L L 0HG RZ RZ 6LOHQW 6 8OWUD R SILENT Notes Can t set POWERFUL and SILENT at the same time 44 ...

Page 45: ...AX2 during powerful operation The compressor s lower limit 8 After the powerful operation is ended the system automatically operates with the previous settings speed is WKYMIN_PW used before the powerful operation the powerful operation Setting Defrosting Inhibit Period DFTIM_OT P5 DFTIM_OT P0 DFTIM_OTP 10 Time Outdoor temperature 1 0 5 C 0 C Notes 1 The first inhibit time after operation start is...

Page 46: ...Hi Defrost signal Preheating judgment Preheating released Indoor fan Hi Med Lo Ultra Lo Outdoor fan Operation lamp Reversing valve Hi or Lo Deceleration period Reverse cycle period 20 MAX 20 MAX Reverse cycle period 3 MAX Preheating Preheating released Stop 15 or more Auto fresh defrosting Hi or Lo ...

Page 47: ...MODEL RAK 18QXD RAK 25RXD RAK 35RXD COOLING CYCLE HEATING CYCLE Outdoor unit Outdoor unit OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT INDOOR UNIT 47 ...

Page 48: ...COOLING CYCLE HEATING CYCLE MODEL RAK 50RXD Outdoor unit Outdoor unit OUTDOOR UNIT INDOOR UNIT OUTDOOR UNIT INDOOR UNIT 48 ...

Page 49: ...and while closing the front panel Shaft Hole 2 1 slightly put it out forward After removing two screws pull the center of the front cover and release the claws Pull the side faces lower sections of the front cover as shown in the figure and remove the CAUTION Remove and attach the front cover to the direction as shown in the figure to ensure no damage occurs to the ECO sensor ECO Sensor X O cover ...

Page 50: ...removethe drain pan 2 Remove the screws from the upper and lower bearing covers 3 Remove the locking hook of the lower bearing cover from the Cabinet Remove two lock screws from the fan motorholder 5 Pull up the evaporator by holding it at the lowerside Insert a screwdriver through the spacebetween the evaporator and drain chute and loosen the fan lock screw to remove the fanand fan motor 1 4 50 ...

Page 51: ...RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 6 5 37 21 2 0 1 5 8 7 23 5 7 21 51 ...

Page 52: ... 㽳 㽲 㽼 㽼 㽲 㽼 㽲 㽼 52 ...

Page 53: ... 䊶 䊶 䊶 䊶 5 䊶 㽵 㽸 700min 1 1 7ms 1200min 1 1 7ms 5V 5V 700min 1 7 1ms 1200min 1 15V 15V 4 2ms 1300min 1 2 1V 5 4V 53 ...

Page 54: ... V 9 54 ...

Page 55: ...s stored in IC531 data will not be erased even when power is turned off Fig 6 1 6 Initial Setting Circuit IC531 1 2 1 8 1 8 1 2 531 Fig 6 2 Initial Setting Circuit IC531 and IC532 For RAK 18QXD only When power is supplied the microcomputer reads the data in IC531 and IC532 E PROM and sets the 2 preheating activation value and the rating and maximum speed of the compressor etc to their initial valu...

Page 56: ...r Voltage of point V 㷄 Room temperature Room temperature input Fig 8 1 Fig 8 2 䃢 A 0V 0V 5V 2 0 1 0 10 20 30 40 3 4 5 10 R402 C403 R407 91 9 Heat Exchanger Thermistor Circuit Heat exchanger temperature is noticed inside the room 1 Preheating 2 Low temperature defrosts at cooling and dehumidification operation time 3 Not working of reversing valve or detection of opening of heat exchanger thermisto...

Page 57: ... 57 ...

Page 58: ... F E D G H D 1V 9 G ˍ ˋ 9 9 H E ˍ ˋ 9 9 F ˍ ˋ 9 9 F 9 5 5 5 5 5 4 5 9 G H D E 9 ˮ ˮ ˮ ˮ ˮ ˮ ˮ 58 ...

Page 59: ...4 terminal 3 terminal 2 terminal 1 terminal 5 ms or 10 ms Fig 12 2 Each stepping motor runs as excited in 1 or 2 phases at 100 PPS or 200 PPS The excitation pattern passes the microcomputer MICON and then the driver IC and excites the coil of each stepping motor Fig 12 1 12 Stepping motor drive circuit Some models not need to install the horizontal sweep motor 39 38 36 35 34 33 37 40 MICON 59 ...

Page 60: ...e infrared sensor will be in operation And a low voltage output from the infrared sensor P W B will be magnified by the amplifier comparator and be transformed the digital signal to microcomputer IC601 The infrared sensor output is Hi when the activity level is not detected On the contrary output is Lo If the connector CN21 is not inserted it will be considered as no infrared sensor and no self di...

Page 61: ...room temperature on the remote controller To improve the dehumidification efficiency performs quiet fan operation Therefore the air is cold and it is not a malfunction It sets to perform dehumidifying operation by setting the temperature slightly lower than remote controller setting 3 3 SERVICE CALL Q A MODEL RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD frost During an automatic run switching the fan s...

Page 62: ...r may cause a gap between the room temperature setting and actual room temperature If there is any difference between the setting and the room temperature adjust the temperature setting to match the living space to a comfortable temperature A4 The difference between the thermometer temperature setting and room temperature will change the rotation speed of the compressor This is not a sign of a bre...

Page 63: ... time The timer cannot be set unless it is set to the current time A1 When set to the current time setting the reading blinks for about 3 minutes Wireless remote control I set the sleep timer during operation But the indoor fan will not run it will not produce wind wind intensity will not change Q5 I tried to change the setting with the room temperature button of the remote control unit in vain Q6...

Page 64: ...N3 2 Remove the P W B from the P W B support CN16 STRUCTURE OF AN INDOOR UNIT ELECTRIC PARTS RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD FIXTURE SCREW FIXTURE SCREW Removing electrical parts 3 Remove three lock screws FIXTURE SCREW ELECTRICAL COVER 1 Remove the electrical parts cover 2 Remove the connectors from the CN4 heat exchange thermistor CN9 CN15 CN19 stepping motor CN2 fan motor and CN16 P W B...

Page 65: ...ll destroy it Be on guard When reconnecting it insert it securely all the way home All the receptacles for connecting tab terminals are with a locking mechanism Forcibly pulling any such receptacle without unlocking it will destroy it Be on guard When reconnecting it insert it securely all the way home Pinch the locking mechanism with your fingers and pull it out unlocked Other instructions 1 Deta...

Page 66: ...oor or outdoor communications is in a failure The product stores 5 last stored failure modes There is a function for deleting memory Once you clear the memory and run the product for several days you can read the failure modes and check them thereby detecting the less frequent failure phenomena Failure modes can be checked by both the blinking of the lamp of the indoor unit and the display of the ...

Page 67: ...nit is blinking troubleshoot the product while referring to the table below 2 If you wish to try another operation while the lamp is blinking operate the START STOP button on the remote control unit twice The first push will reset the indoor microcomputer while the second will activate the product Self diagnosis display function indoor side display An example of 5 time blinking 2 second intermissi...

Page 68: ...69 68 ...

Page 69: ... times Indoor interface circuit broken communication error between indoor and outdoor units 1 Indoor interface circuit Outdoor interface circuit broken 1 Outdoor interface circuit 69 020 00 ECO sensor unit defective Short circuit ECO sensor circuit ...

Page 70: ...pped Temporary operation SW How to stop the operation Press and hold the Temporary operation SW again Or stop the operation using the remote controller During the forced cooling operation the Timer indicator blinks twice When performing the forced cooling operation turn the power off once If you press and hold the switch for 5 sec or longer the forced cooling operation starts To stop the forced co...

Page 71: ...3 and page 38 7 71 ...

Page 72: ...Please set the DIP switch No 6 to ON accordingly Refe to page r 57 RAR 6N1 RAR 6N2 RAR 6N3 RAR 6N4 RAR 6N5 72 ...

Page 73: ...57 73 ...

Page 74: ... 74 ...

Page 75: ...dicated then release START STOP button and Mon Sun button Remote controller now enters Intermittent Fan Control Change Mode Default Pattern 1 HOW TO CHANGE THE INTERMITTENT FAN CONTROL SETTING 2 Press ROOM TEMPERATURE setting UP V DOWN buttons The intermittent pattern changed with indoor unit beep sound Transmission sign lights up with beep from indoor unit simultaneously Pattern 1 Pattern 2 Patte...

Page 76: ...p with beep from indoor unit simultaneously Beep sound pattern 1 Default setting Short beep Beep sound pattern 2 Changed setting Double beep HOW TO CHANGE THE FAN SPEED IN COOLING MODE DURING THERMO OFF Beep sound pattern 2 Changed setting Double beep NOTE 1 The selected fan speed will remain unchanged after the unit is turned off 2 If Timer reservation has been set it will be canceled 3 During ti...

Page 77: ...e sunshine operating hours and other factors of the day so that the phenomenon may not be able to be identified at the time of a repair service visit In that case too use the self diagnosis memory function Ć2 The outdoor self diagnosis display overload lower limit cut and OH thermistor heat up can be identified only when you are using the self diagnosis lamp of the outdoor unit and the self diagno...

Page 78: ...Check 3 Is the compressor of the outdoor unit running Yes No If you responded No to Check 2 ǂǂǂCheck 4 Does the emergency operation switch work Yes No First check the failure phenomenon and status and then move on to elaborate diagnosis Initiating troubleshooting No Yes Turn off the power wait at least 5 seconds turn it back on and observe the way the horizontal vanes move for about 30 seconds ǂǂǂ...

Page 79: ... phase 3 wire power supply If the 3 15 A fuse has blown out eliminate the cause of the fuse blowout Otherwise there will occur another fuse blowout If the 3 15 A fuse has blown out due to an abnormally high voltage to the power supply the varistor VA001 will deteriorate and become destroyed as well On a repair service visit due to the failure phenomenon of The power will not become turned on take ...

Page 80: ...ls Instruct your users to use new alkaline batteries Does the remote control unit have a sufficient battery capacity If the liquid crystal display becomes extremely faded when a remote control signal is sent replace the batteries No Press the reset switch of the remote control unit then conduct another operation check Has the product worked Yes Instruct your users to be sure to press the reset swi...

Page 81: ...it output usually shows a noise waveform as shown in ǂthe right hand figure In the case of slight jamming this kind of waveform ǂwill not cause practical problems However intense degrees of jamming ǂwill disable the reception of remote control signals When the fluorescent lamp is old and is flickering it may cause disorders ǂin the reception of remote control signals Actions proposed 1 Make it har...

Page 82: ...s coming from other electrical products Turn on and off the electrical products turn off the power and turn on the power and check their effects on the reception of remote control signals For products whose operating states change check the effects of each state Actions proposed Change the location relationship between the air conditioner and the target products Use a different wall outlet for the...

Page 83: ...e of the indoor unit blinking Yes Yes Yes No No No Check for failures according to the self diagnosis display Did the self diagnosis lamp LD301 of the outdoor unit blink once or become turned off Check for failures according to the self diagnosis display Remove the connector CN4 of the room temperature thermistor and heat exchanger thermistor and measure the thermistor resistance Did the reading r...

Page 84: ...timated failure locations Indoor fan motor Fan motor drive circuit Diagnosis flow Initiating troubleshooting Yes Replace the indoor fan motor No Replace the indoor electrical parts Run the product by remote control and then stop it Reproduce the failure phenomenon Is the voltage between pins ĺ and ļ of the fan motor connector CN2 below 1 5 V Take measurements while the failure phenomenon is presen...

Page 85: ...ed the self diagnosis way to check out there is no fault but low sensitivity false action is also occur please check as follows Structure confirm Is the structure and appearance of frensnel lens ok Please confirm whether there any dirt or nick on it Please confirm whether frensnel lens is loose Does the structure of the sensor P W B have any problem Note Ć The infrared sensor detects changes to in...

Page 86: ...nt before inserting it into the terminal board securely Detach the connector CN3 from the terminal board temperature fuse and check the temperature fuse for continuity Is the resistance almost 0 No Yes Initiating troubleshooting Replace the indoor electrical parts Replace the terminal board Estimated failure locations Outdoor unit error Please confirm the times of the LD301 blinking and then Situa...

Page 87: ...nks 9 times and the product will not run Estimated failure location 䊶 Loose connector wire break or short circuit in the room temperature thermistor heat exchanger thermistor Cautions 䊶 Starting the product by remote control will initiate failure detection Merely turning on the power will not activate the failure detection function Diagnosis flow Initiating troubleshooting Yes Yes No No Correct th...

Page 88: ... the indoor fan motor Indoor fan motor mechanically locked Indoor fan motor Indoor fan motor drive circuit Diagnosis flow Initiating troubleshooting No No No No No No No Yes Yes Yes Remove the cause of the mechanical lock Is the indoor fan motor connector CN2 securely inserted Is it free of wire breaks Correct the connector and wiring For 2 to 3 seconds after startup by remote control did a voltag...

Page 89: ...om errors Yes Yes Yes Yes No No No No Correct the F cable connection Is the CN securely inserted into the outdoor board Correct the connector Press the START STOP button on the remote control unit and start the product Are terminals 1 and 2of the terminal board of the electrical parts of the outdoor unit subjected to 㶎Take measurements within 3 minutes after remote control operation Check the elec...

Page 90: ...ssory Part SPX CFH25 31 36 41 34 5 18 27 25 24 26 19 12 13 32 16 17 15 42 39 3 2 11 4 8 10 33 38 37 29 28 30 45 43 46 23 47 1 9 44 48 49 50 50 51 7 INDOOR UNIT MODEL PARTS LIST AND DIAGRAM RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 52 90 ...

Page 91: ...UNTING PLATE 40 2 AIR FILTER 41 1 TER COVER 42 1 RE HOLDER 43 2 F CASE 44 1 T PLATE 45 1 HORIZONTAL AIR DEFLECTOR 1 46 1 HORIZONTAL AIR DEFLECTOR 2 47 1 K PANEL 48 1 CABI PLATE 49 1 SUPPORT P W B 50 2 BUTYL 51 1 BUTYL 52 1 FUSE 3 15A NO HWRAK 50RXD A01 HWRAK 50RXD A02 HWRAK 25RXD A03 HWRAK 25RXD A04 HWRAK 50RPB 903 HWRAK 50RPB 904 HWRAK 35PPB 929 HWRAK 25PXB 922 HWRAK 25PXB 923 HWRAK 25PXB 924 HWR...

Page 92: ...RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD JCH WH NO 0111E 92 ...

Reviews: