1. Failure phenomenon: The power will not become turned on.
>
Situation
@ǂ
Neither initialization, remote control, nor any other step works on the vane position at power-on.
[ Estimated failure
locations ]
·
3.15 A fuse blown out
·
Control power circuit
·
Connector loose, wire break
>
Cautions
@
>
Diagnosis flow
@
Initiating troubleshooting
Is a voltage of
2 0 V applied between WR2-WR4
ǂǂǂǂǂǂǂǂǂ
Is the CN16 securely connected?
Replace the "indoor electrical parts".
Replace the "indoor electrical parts".
Replace the "3.15 A fuse".
Replace the "varistor (VA001)".
Abnormal
Is the power supply voltage normal?
Has the varistor VA001 not become burned?
Normal power supply voltage: AC 230 V
Estimated cause of fuse blowout
·
Abnormally high voltage applied to the power supply
·
Indoor fan motor out of order
·
Power circuit out of order
·
Before work, check the power supply voltage. An abnormal voltage may be being supplied in
some rare occasions due to a defect in the indoor wiring (a wire break in the neutral wire of the
single-phase 3-wire power supply).
·
If the 3.15 A fuse has blown out, eliminate the cause of the fuse blowout. Otherwise, there will occur
another fuse blowout.
·
If the 3.15 A fuse has blown out due to an abnormally high voltage to the power supply, the varistor
(VA001) will deteriorate and become destroyed as well.
·
On a repair service visit due to the failure phenomenon of "The power will not become turned on",
take a "3
A fuse" and a "varistor" with you.
Get the indoor wiring back to its
normal condition, then conduct
a final check.
Normal
No
No
No
No
Yes
Yes
Yes
Yes
Yes
Replace the 3.15 A fuse, disconnect the CN2
(indoor fan motor), and conduct an operation
check. Has the product worked?
Replace the "indoor fan motor".
Another fuse blowout
Disconnect the CN2 and check for continuity
between the "red" and "black" wires of the
indoor fan motor by using a tester. Is it short-
circuited?
Apply the black lead of the tester to the red
lead of the motor. Apply the red lead of the
tester to the black lead of the motor.
Replace the "indoor electrical
parts".
Replace the "indoor fan motor".
Replace the "indoor electrical
parts".
Reconnect the connector correctly.
3
?
AC
.15
Is DC 5 V applied to both ends of the C106 and C113?
- 79 -
Summary of Contents for RAC-25WXD
Page 2: ... DANGER 2 ...
Page 31: ...WIRING DIAGRAM RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 31 ...
Page 33: ...CIRCUIT DIAGRAM MODEL RAK 18QXD 33 ...
Page 34: ...CIRCUIT DIAGRAM MODEL RAK 25RXD RAK 35RXD RAK 50RXD 34 ...
Page 51: ...RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD 6 5 37 21 2 0 1 5 8 7 23 5 7 21 51 ...
Page 52: ... 㽳 㽲 㽼 㽼 㽲 㽼 㽲 㽼 52 ...
Page 54: ... V 9 54 ...
Page 57: ... 57 ...
Page 68: ...69 68 ...
Page 71: ...3 and page 38 7 71 ...
Page 73: ...57 73 ...
Page 74: ... 74 ...
Page 92: ...RAK 18QXD RAK 25RXD RAK 35RXD RAK 50RXD JCH WH NO 0111E 92 ...