– 113 –
HOW TO OPERATE USING THE SERVICE SWITCH THE OUTDOOR UNIT
1. Turn off the power supply to outdoor unit and then turn on again.
2. Remove the electrical box cover.
LD303 (red) will light and the unit will operate in the forced cooling mode at this time.
Never operate the unit for
more than 5 minutes.
(Cautions)
(1) If interface signal (DC 35V) terminals C and D are not connected when the outdoor unit is in forced cool mode, the outdoor
unit defect indicator (LD301) will blink 9 times during operation to indicate communication error.
(2) If checking is done with the compressor connector disconnected, the unit will continue normal operation when the
electrical parts are normal, or it will repeat operating for approx. one minute and stop due to overload power limit cut,
or it will operate in the overload status.
Be sure to push the service switch again to stop the forced cool operation.
HOW TO OPERATE THE OUTDOOR UNIT INDEPENDENTLY
The operation method is the same as “How to operate using the connector to servicing the outdoor unit”.
1 The charging amount of 300g is equivalent to the load in normal operation.
Charge refrigerant of 300g
after vacuuming ( 1 )
Do not operate for more than 5
minutes
Parts to be prepared
(1) Reducing union
2/8” (6.35mm)
1/2” (12.7mm)
(2) Copper pipe (2/8” and 1/2”)
1. Connect the large dia. pipe side and small dia. pipe side service valves using a pipe.
Large dia. service valve
Reducing union
(2/8” and 3/8”)
Copper pipe
(2/8”)
Small diameter
service valve
Reversing
valve
Compressor
Outdoor unit
Connect the small diameter
service value and the large
diameter service valve using the
reducing union and copper pipe
as shown on the right.
Electrical Box Cover
Self diagnosis lamps
(LD303, 302, 301)
Service switch
(forced-cooling mode is set by
pressing for 1 second or more,
and stopped by pressing again.)
Summary of Contents for RAC-65NH5
Page 36: ...CIRCUIT DIAGRAM 37 ...
Page 37: ...CIRCUIT DIAGRAM MODEL RAC 65NH5 39 ...
Page 87: ... 99 SELF DIAGNOSIS LIGHTING MODE ...
Page 89: ... 101 2 Outdoor unit does not operate but receives remote infrared signal ...
Page 91: ... 103 6 Check the main P W B power circuit ...
Page 92: ... 104 CHECKING THE REMOTE CONTROLLER ...
Page 97: ... 109 ...
Page 107: ...HITACHI PM NO 0000E Printed in Malaysia RAK 65NH5 RAC 65NH5 ...