2. Indoor fan does not operate (others are normal)
Can the fan be stopped by remote
control?
The microcomputer fan PWM
Replace the microcomputer
.
Replace the fan motor.
Replace the microcomputer.
Perform final operation check.
Are pulse signals output at
microcomputer pins 15 - 18 when
auto swing is turned on in the fan
mode?
Replace the microcomputer.
Is a voltage over 15 or below 10V
being generated on the 12V line?
No
No
No
No
Perform final operation check.
output (at pin 24 ) is 1 - 5V.
Check IC711. If it is normal,
replace the air deflector motor.
Replace IC111.
3. Air deflector does not move (others are normal)
Yes
Yes
Yes
Yes
4. Check the control P.W.B. (power circuit)
Is 35V or 20V being output
at pin 5 relative to 0V at
pin 3 of CN3?
Is 12V or 7V being output
at (+) relative to 0V at (-) of
C114?
Is ICP1 normal?
Normal if it is less than 1 .
Blown (open) if it is 1 or more.
Replace ICP1. Check if the air
deflector motor is shorted, and
IC111, Q111, C114, ZD121 are
defective.
If shorted / defective, ICP1 will be
open again.
Replace the terminal board.
Insert the connection cable
securely.
Replace IC121. Check if a short
occurs in the 5V line.
If the 5V line is shorted, ICP1 will
be open again.
Check to see if the connection cables are
disconnected or reversed.
If normal, check the outdoor unit P.W.B.
Has the terminal board
thermal fuse blown (open)?
Replace Q111 and IC111.
Is DC5V being generated?
Perform final operation check.
: When the unit is not in operation, the voltage across the 35V line may drop to 20V.
: When the unit is not in operation, the voltage across the 12 V line may drop to 7V.
1
Yes
Yes
(Normal)
Yes
(Open)
Yes
No
No
No
Yes
No
No
2
2
1
-