LD301 blinks 6 times.
The temperature at the OH thermistor rises.
Is the thermistor circuit normal?
Replace par
ts in the
thermistor circuit.
LD301 blinks 5 times.
Overload lower limit cut.
Replace the main
P.
W
.B.
Check to see if the refrigerating cycle is defective. Check the indoor
unit for clogged heat exchanger
or filter
.
Check the outdoor
unit for defective shielding.
LD301 blinks 4 times.
Failure of switching.
Is the 15V power supply output normal? (Main P
.W
.B. display)
Is the intelligent power
module (
IPM) normal?
(Inverter section)
The intelligent main module may be defective. Replace the main
P.
W
.B.
See “System Power
Module Diagnosis”.
With CN3 and CN4 disconnected, is the 15V
output between
“15V” and
”15-0V” on the main P
.W
.B.?
Replace the main
P.
W
.B.
LD301 blinks 3 times. Abnormal low speed.
Ye
s
Ye
s
Ye
s
Ye
s
Ye
s
Ye
s
Yes
No
No
No
No
No
No
No
※
※
※
※
- 88 -