2
.
TROUBLESHOOTING
Fault
code
Fault description
Possible
r
eason
s
f
or
a
bnormality
How to
d
eal
w
ith
Remarks
74 Indoor EEPROM
Data 2 fault
EE in MCU fails, the unit
can run, but the function
user has set is ineffective.
Replace EE data in MCU.
81
Indoor ambient
Temperature
Sensor Fault
1. The cable of the room
temperature sensor is connected
loosely;
2. The room temperature sensor
fails;
3. The sampling circuit is abnormal.
1. Reconnect the cable of the
room temperature sensor;
2. Replace the room temperature
sensor;
3. Replace the indoor control
board.
83
Evaporator Middle
Temperature
Sensor Fault
1.The cable of the coil temperature
sensor of the evaporator fails;
2.The coil temperature sensor of
the evaporator fails;
3.The sampling circuit is abnormal.
1. Reconnect the cable of the
coil temperature sensor of the
evaporator;
2. Replace the coil
temperature sensor of the
evaporator;
3. Replace the indoor
control board.
FE
(254)
Communication
between main
control board &
Wired controller
Fault (display on
wired controller)
1. The wired controller and the
indoor control board are
connected loosely.
2. The sequence of the wiring
between the wired controller
to the indoor control board is
wrong;
3. The wiring between the
wired controller to the indoor
control board fails;
4. The wired controller is fails;
5. The indoor control board
is abnormal.
1.
2.
Reconnect the wiring between
the wired controller to the
indoor control board;
Replace the wiring between
the wired controller to the
indoor control board;
3. Replace the wiring between
the wired controller to the
indoor control board;
4. Replace the wired controller;
5. Replace the indoor control
board.
ER
Communication
between main
control board
& display board
Fault (displays on
display board)
1.The wiring between the display
board to the indoor control
board is connected loosely;
2.The sequence of the wiring
between the display board to the
indoor control board is wrong;
3.The wiring between the display
board to the indoor control
board fails;
4.The display board fails;
5.The indoor control board fails.
1. Reconnect the wiring
between the display board
to the indoor control board;
2. Replace the wiring between
the display board to the
indoor control board;
3. Replace the wiring between
the display board to the
indoor control board;
4. Replace the display board;
5. Replace the indoor control
board.
27