4.10
Checking the binary input/output circuits
M11722-2 v4
Do not insert anything else to the female connector but the corresponding male
connector. Inserting anything else (such as a measurement probe) may damage the
female connector and prevent a proper electrical contact between the printed circuit
board and the external wiring connected to the screw terminal block.
4.10.1
Binary input circuits
M11722-4 v3
Preferably, disconnect the binary input connector from the binary input cards. Check all connected
signals so that both input level and polarity are in accordance with the IED specifications.
4.10.2
Binary output circuits
M11722-8 v3
Preferably, disconnect the binary output connector from the binary output cards. Check all connected
signals so that both load and polarity are in accordance with IED specifications.
4.11
Checking optical connections
M16022-2 v8
Check that the Tx and Rx optical connections are correct.
An IED equipped with optical connections has an minimum space requirement of
180 mm for plastic fiber cables and 275 mm for glass fiber cables. Check the
allowed minimum bending radius from the optical cable manufacturer.
1MRK 511 403-UEN Rev. L
Section 4
Starting up
Bay control REC670
47
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Summary of Contents for REC670
Page 1: ...Relion 670 SERIES Bay control REC670 Version 2 2 IEC Commissioning manual ...
Page 2: ......
Page 28: ...22 ...
Page 54: ...48 ...
Page 60: ...54 ...
Page 66: ...60 ...
Page 90: ...84 ...
Page 212: ...206 ...
Page 218: ...212 ...
Page 232: ...226 ...
Page 240: ...234 ...
Page 241: ...235 ...