105
Parameter tables
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
4.10. PArAMETEr TABlES
4.10.1 Installer Parameters
Setting Instructions
•
Please refer to the System Controller Installation & Operation Manual for instructions on how to set the installer
parameters.
Id
Parameter
Conf
description
Min
Max
Step
default
CONF
System Configuration
12345 Set according to the type of hydraulic
configuration installed.
1
5
1
3
P1
DHW Configuration
123-5
Set to 0=No DHW, 1=DHW valve, 2=DHW pump
0
2
1
0
P2
Secondary Pump
12---
Set to 1 if a buffer/hydraulic separator and a
secondary pump is used (CONF 1 or CONF 2
only)
0
1
1
0
P3
Pump Overrun Time
12345 Sets how long the pumps run after the heating is
switched off.
1
10
1
2 min.
P4
OTC Heating Curve
Gradient
12345 Sets the heating curve for OTC control function
0.2
2.2
0.1
1.1
P5
Minimum Supply
Temperature
12345 Sets the minimum supply water temperature for
the heating.
5
40
1
15°C
P6
Zone 1: Maximum
Supply Temperature
12345 Sets the maximum supply water temperature for
the heating (zone 1)
20
55/65/
90*
1
55°C
P7
Room Compensation
Factor
12345
Sets the room temperature influence for the OTC
control function
0
5
0.5
2
P9
Actuator Run Time /
Mixing valve Control
---45
Set to the running time of the actuator (see
actuator manufacturer’s technical data)
30
600
10
120 s
P10 DHW setpoint
(not available if P1=0)
123-5 Setpoint for the DHW control function.
45
65
1
45°C
P11 DHW differential
(not available if P1=0)
123-5 DHW control differential
1
10
1
5 K
P12 DHW supply offset
(not available if P1=0)
123-5
Influences how quickly the hot water tank is
heated
1
30
1
10 K
P15
Maximum Outdoor
Temperature for Boiler /
Electric Operation.
-2345
Boiler / Electric heater will be disabled above
this temperature (Heat Pump works on its own).
OFF means the boiler/electric heater is always
enabled.
-20
20, then
OFF
1
0°C
P14
Heat Pump Minimum
Outdoor Temperature
(Config 3,4,5 only)
--345
Heat Pump Operating Limits: Defines the lowest
possible outside temperature of operation of the
heat pump.
-25
20,
then
OFF
1
-20°C
P17 Boiler Minimum ON
Time
--345 Sets the minimum ON time of the boiler to reduce
inefficient short-cycling
1
30
1
2 min
P18 Boiler minimum OFF
time
--345 Sets the minimum OFF time of the boiler to
reduce inefficient short-cycling
1
30
1
5 min.
P19 Waiting Time for Boiler/
Electric Heater
-2345
Sets the minimum time the controller will wait
(after the heat pump is switched on) before using
the boiler or electric heater
1
90
1
30 min.
P21
Minimum Supply
Setpoint during Frost
Protection
12345 Sets the minimum supply water temperature when
the frost protection function is active.
10
35
1
20 °C
P22 Frost Protection
Activation Temperature
12345 Sets the outdoor temperature below which the
frost protection function will activate.
-20,
then
OFF
5
1
2°C
P23 Zone2: Maximum
Supply Temperature
12345 Sets the maximum supply water temperature for
the heating (zone 2 extension)
20
55/65/
90*
1
50°C
P24
Configuration of Tariff/
Timer Input
12345 The sets the meaning of the digital input “Tariff/
Timer”
0
4
1
4
P25 Start Screed-Drying
Function
12345
Set to 1 to start immediately the underfloor
screed-drying function
0
1
1
0
P26 Summer switch-off
temperature
12345 Sets the daily average outdoor temperature above
which the heating will be switched off.
10
25, then
OFF
1
20°C