Controller pack
Service Manual
4
4.16.2 System component connections
Heat pump
•
The System Controller controls the heat pump outlet water temperature by a 4-20mA signal. When there is no demand for
the heat pump to be on, the System Controller directly switches the heat pump off. The heat pump can signal to the System
Controller when it has a fault so that a fault code can be displayed and appropriate action taken.
21
6
5
31
TERMINAL
BLOCK C
4-20mA
TERMINAL BLOCK A
Heat Pump
/
N
O
FF
O
2
1
note
The 4-20mA signal is polarity-sensitive. Connect the wires as shown. Please refer to heat pump installation
-
manual for terminal connections.
Three- stage electric heater
•
In a mono-energetic system (CONF 2), the electric heater is used if required to increase the supply water temperature.
P19 Waiting time for boiler/electric heater
9
8
7
TErMInAl BloCK A
Output 1
Electric Heater
N
Output 2
Boiler
•
In a Bi-Valent System (CONF 3,4,5), the boiler is used when the heat pump cannot achieve the desired supply temperature
on its own. Set the minimum on and off times (P17 and P18), according to boiler type, to prevent inefficient short-cycling.
P17 Boiler Minimum ON Time
P18 Boiler Minimum OFF Time
P19 Waiting time for boiler/electric heater
12
11
10
9
8
7
6
5
Boiler
ON/OFF
Boiler
Pump
(CONF3)
Boiler
Pump
(CONF4)
TERMINAL
BLOCK A