Controller pack
Service Manual
118
System configurations
SMGB0066 rev.0 - 12/2009
TERMINAL
BLOCK C
TERMINAL
BLOCK C
TERMINAL
BLOCK C
T MIX
T DHW
T RET
T SUP
T EXT
10
9
5
4
3
2
1
15
14
4.17. SySTEM ConfIGUrATIonS
Mono-valent systems ‘conf 1’
¡
The Heat Pump is sized to provide 100% of the heating requirements on the coldest day of the year. Used in new builds or in
boiler-replacement applications.
• Direct OTC Controlled Heating Loop
• Optional DHW storage with diverting valve or pump
This configuration is suitable for low-temperature radiators and underfloor heating systems.
● Important settings
• Set installer parameter CONF to value 1
• Set installer parameter P1 to 0 (no DHW), 1 (DHW valve) or 2 (DHW pump)
• Set P4 (OTC heating curve) according to building/ system
● Additional settings
•
Set installer parameter P2 to 0 (no secondary pump), 1
(secondary pump9, if buffer tank or hydraulic separator is used
•
DHW setpoint and control parameters
•
Minimum and maximum supply temperatures
•
Room temperature compensation
•
Frost Protection parameters
•
Summer switch-off setting
•
Tariff/ Timer input configuration
- Heat Pump
- Optional DHW valve/ pump
- Optional secondary pump
- Optional DHW electric heater