119
System configurations
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
● dHW electric heater
The system controller can switch a DHW storage electric heater to achive higher DHW temperatures. The electric heater
should have its own thermostat set to a higher value than the DHW setpoint of the system controller. Please take care about
the type of DHW storage tank fitted and the position of the electric heater.
Terminal block C (inputs)
Terminal block A (outputs)
Terminal block B (Power Supply)
Return sensor
Supply sensor
Outdoor sensor
Heat pump control
output
Heat pump fault
Tariff/ Timer input
DHW sensor
RF Receiver
-
+
T RET
4-20mA
T SUP
T DHW
T EXT
12
11
10
9
8
7
6
5
4
3
2
1
15
14
13
DHW Heater
enable
DHW
Valve/Pump
Secondary
pump
Heat pump
remote on/of
f
ON/
OFF
12
11
10
9
8
7
6
5
4
3
2
1
N
N
L
15
14
13
Mono-energetic systems ‘conf 2’
¡
The Heat Pump is sized to provide around 60% of the heating requirements on the coldest day of the year, and will typically
provide 90-95% of the heating requirements over the whole heating season. An electric auxiliary heater is used to provide
the additional heating required on cold days (additional capacity and/or higher temperature). Used in new builds or in boiler-
replacement applications.
• Direct OTC Controlled Heating Loop
• Optional DHW storage with diverting valve or pump
• 3-stage electric heater
● Important settings
• Set installer parameter CONF to value 2
• Set installer parameter P1 to 0 (no DHW), 1 (DHW valve) or 2 (DHW pump)
• Set P4 (OTC heating curve) according to building/ system
• Set P33 (return temperature limit offset) to value 5 K
● Additional settings
•
Set installer parameter P2 to 0 (no secondary pump), 1
(secondary pump), if buffer tank or hydraulic separator is
used
•
DHW setpoint and control parameters
•
Minimum and maximum supply temperatures
•
Room temperature compensation
•
Frost Protection parameters
•
Summer switch-off setting
•
Tariff/ Timer input configuration
- Heat Pump
- 3-stage electric heater
- Optional DHW valve/ pump
- Optional secondary pump
- Optional DHW electric heater