Controller pack
Service Manual
126
System testing
SMGB0066 rev.0 - 12/2009
Id
Parameter
Conf
description
Min
Max
Step
default
Setting
P33
Return temperature
limit offset
-2345
Control parameter to prevent electric heater use when the
return temperature is too high for heat pump operation.
1,
then
OFF
15
1
OFF
P34
DHW electric heater
waiting time (not
available if P1=0)
12---
Sets the time to wait after starting to heat the DHW tank
before enabling the special output for “DHW electric heater
enable”.
0
60
1
45 min.
P35
Mixing valve opening
delay time
---45
Or solid fuel or oil fired boiler. Prevents the mixing valve
opening for the set delay time to allow the boiler to heat up.
1,
then
OFF
20
1
OFF
note
Operational data shown depends on the system configuration (CONF) setting.
-
Zone 1 is the heating loop controlled by the System Controller.
-
Zone 2 is the heating loop controlled by the Extension Controller.
-
*
Maximum supply temperature limit depends on configuration
CONF 1:
limit = 55°C
CONF 2:
limit = 65°C
CONF 3,4,5:
limit = 55°C
4.20. SySTEM TESTInG
4.20.1. System start-up
After the installation of sensors and outputs, the
System Controller
controller can be started for the first time.
Switch on the mains power supply.
The controller will be initialised with the default configuration stored in the internal memory.
A test procedure is performed to check the validity of the data in the internal memory, and the various inputs are tested. All
sensors and communications devices are automatically detected. All faults and warnings are automatically reset and the
software version is displayed for reference.
4.20.2. SySTEM TEST
Once the system has been installed, it is recommended that the following tests are carried out:
Check that you have selected the correct configuration, and that the necessary installation parameters have been set.
1.
Check the wiring of the inputs and outputs. Use the procedure in 7.3 to view the temperature sensor values. Using the
2.
procedure in 4.20.4, it is possible to manually override the outputs to test the system operation.
Check that the Room Unit is communicating with the RF Receiver. To do this, change the temperature setpoint on the
3.
Room Unit to the maximum or minimum value and check that the heat pump reacts appropriately