Controller pack
Service Manual
128
Expanding the system
SMGB0066 rev.0 - 12/2009
normal operation mode
output display mode
output Setting mode
& > 1 sec.
SET
SET
SEL
ID
Output
Min
Max
CONF
HPS
Heat Pump setting (mA)
2
20
12345
HP
Heat Pump remote on/off
0
1
12345
PO2
Secondary pump (not displayed if P2=0)
0
1
12345
DHWV
DHW valve/pump (not shown if P1=0)
0
1
123-5
EHS1
Electric heater output 1
0
1
-2---
EHS2
Electric heater output 2
0
1
-2---
DHWE
DHW electric heater enable (not shown if P1=0)
0
1
12---
PO1
Boiler pump
0
1
--34
BLR
Boiler on/off
0
1
--345
V
Mixing valve position (%)
0
99
---45
Operational data shown depends on the system configuration (CONF) setting.
4.21. ExPAndInG THE SySTEM
4.21.1. Additional mixing zone
The system controller is designed so that it can be expanded when necessary to control heating systems with an additional
mixed heating zone. The extension controller will control a mixing circuit, consisting of a mixing valve and pump as shown
below. It is possible to use one room unit for the entire system, or have one room unit in each heating zone with separate
time programmes.
Installation instructions are included with the extension controller.