Controller pack
Service Manual
144
Yutaki unit PCB
SMGB0066 rev.0 - 12/2009
4.24. yUTAKI UnIT PCB
PCB drawing
•
The PCB in the Yutaki unit operates with nine DIP switches, six LEDs and two rotary switches. The location is as follows:
lEd indication
function
LED 1
Power supply indication
LED 2
LED 3
LED 4
Operation status indication
LED 5
Alarm indication
LED 6
Setting mode indication
Switch indication
DSW1
Optional functions
DSW2
Unit control configuration / Unit HP
DSW3
Unit control configuration
DSW4
Unit model configuration
DSW5
Not used
DSW6
End resistance / Fuse recovery
DSW7
Unit control configuration
DSW8
Setting Pd Pressure Sensor Type
DSW9
Setting Ps Pressure Sensor Type
rotatory switch
RSW1 & RSW2
Heating setting temperature
RSW3 & RSW4
Not used
SSW
UP=”+ Temp.” / DOWN=”-Temp.”
Jumper setting
JP2
Cut
⇒
Re-Start after power failure
note
The mark “
-
” indicates position of dips switches. Figures show
setting before shipment or after selection.
Not mark “
-
” indicates pin position is not affecting.
note
Before setting dips switches, firstly turn off power source and
-
set the position of the dips switches. If the switches are set
without turning off the power source, the contents of the setting
are invalid.
Segment
Indication
SEG1 / SEG2
Unit Status
SEG3, SEG4, SEG5
Discharge and Suction pressure value
alternatively
1. Status indication.
Press the PSW2 more than three seconds to change the
status display mode.
2. Alarm history
Press the PSW1 and PSW2 together more than three
seconds to switch to alarm history mode.