149
Safety and control device setting
SMGB0066 rev.0 - 12/2009
Controller pack
Service Manual
4
Yes
Yes
Yes
No
No
No
1. Zero Reset Control
Expansion Valve 100 Pulse
2. Startup Control I
(operation with Fixed Opening)
5. Stop Control
3. Startup Control II
(TdSH Control Operation)
6. Zero Point Control
4. Normal Control
(TsSH Control Operation)
Fo > 0
F > 0
F = 0
7. Forced Opening Control to
Protect Product
4.25.2. Control of expansion valve
Abasic flow for the expansion valve drive assuming long compressor operation time.
See sections from the next page for details in each procedure (Details of Performance, Shifting Conditions).
F: INV (Compressor)
Real Operation Frequency (Hz)
Fo: INV (Compressor)
Order Frequency (Hz)