153
Compressor ON/OFF control
SMGB0066 rev.0 - 12/2009
Available Optional
functions
Service Manual
5
Jumper lead setting (JP2): Automatic restart after power failure
•
Keep the same status as before. Setting before shipment:
JP2
1
0 = open; 1 = Short circuit
The function selection using the jumper lead setting is shown in the table below.
Setting
function
details
0
Enable
If this function is 'Enable', in case of power failure the unit will restart
automatically once the power is recovered
1
Disable
5.3. CoMPrESSor on/off ConTrol
ON/OFF Temperature Differential (Thermo-ON/OFF Difference) is configurable by 1 ºC, i.e., “1, 2, 3, 4” by setting mode
operation. The factory setting (default) is “4 ºC”.
This mode is activated by turning pin 3 of DSW1 ON.
Pressing PSW2 and PSW1 for more than three seconds at the same time allows changing from each item displayed. To
finish changing, press PSW2 and PSW1 for more than three seconds again after changing to predetermined setting.
The chart of setting operation is shown below.
PSW1
PSW1
PSW1
PSW2
PSW1 ( )
PSW2 ( )
PSW2
PSW2
PSW1: Valve up
PSW2: Valve down