159
Test run procedure for Yutaki
SMGB0066 rev.0 - 12/2009
Test run
Service Manual
6
Parameters check using 7-Segment
•
Press PSW2 more than 3 seconds. Now you can consult the Yutaki parameters by pressing PSW2 (up) or PSW1 (down).
Code (Upper side)
Content
Code (Upper side)
Content
. .
Operation status
Liquid refrigerant temperature
Pd
Evaporating temperature
Ps
Ts
Chilled water setting
temperature
Exp. V pulse
.
Chilled water setting
temperature 2
Compressor Hz
Hot water setting
temperature
Fan stop
.
Hot water setting
temperature 2
Manual defrost ON (if PSW1
& PSW2 pushed together for
3 sec.)
Water inlet
.
ROM No.
Water outet
Model identification
Ambient
temperature
Optional Function selection
status
Td
-
-
Pump single operation
•
PSW1+ PSW2
PSW1+ PSW2
PSW1
PSW2
Blink (2.5 sec ON, 0.5 sec OFF)
or
Stop Signal
(Behavior)
"PSW1+2" turns ON only pump.
note
Pump feed-back abnormality does not turn OFF the pump.
-