Test run procedure for Yutaki
SMGB0066 rev.0 - 12/2009
Test run
Service Manual
6
6.2.1.2. System test
Once the system has been installed, it is recommended that the following tests are carried out:
Check that you have selected the correct configuration, and that the necessary installation parameters have been set.
1.
Check the wiring of the inputs and outputs. Use the procedure in 7.3 to view the temperature sensor values. It is possible
2.
to manually override the outputs to test the system operation.
Check that the Room Unit is communicating with the RF Receiver. To do this, change the temperature setpoint on the
3.
Room Unit to the maximum or minimum value and check that the heat pump reacts appropriately.
6.2.1.3. reviewing the operational data
The table below shows the values that are available to be viewed during Normal Operation mode. These can be shown by
pressing the button
Abbr.
operational data
Units
Conf
Sensor
Temperatures
TEXT
Outdoor temperature
°C
12345
TSUP
Supply water temperature
°C
12345
TMIX
Zone1: Mixed supply temperature
°C
---45
TRET
Return temperature
°C
12345
TDHW
DHW temperature
°C
123-5
TR1
Room temperature
°C
12345
V
Mixing valve position
-
---45
FAUL
Fault status
-
12345
Controller Setpoints
SSUP
Overall system supply setpoint
°C
12345
S1
Zone1: supply setpoint
°C
12345
SR1
Zone1: room setpoint
°C
12345
S2
Zone2: supply setpoint
°C
12345
DSET
DHW setpoint
°C
123-5
SDHW
DHW supply setpoint
°C
123-5
Normal Operation mode