Troubleshooting
Service Manual
174
Incidents of operation
SMGB0066 rev.0 - 12/2009
7.1.3. Incidents of operation
The operation of the heater is bonded to the Yutaki heat pump.
(If that is in default, the heater can be activated only if specific programming controller Yutaki is done). The heater can be
activated by the controller Yutaki under request for additional power or temperature.
In case of non-functioning heater should check:
- That signals to the heat pump function.
- That fuse protection heater in a state.
- That the water pressure is at least 1 bar.
- That the water flow is assured permanently.
If the above checks are correct:
- Turn off the heater isolating fuses.
- Open the hood of connecting the heater.
- Check the good son tightening supply and command.
Press firmly on the push rearmament security heat between the 2 relays electrical power to rearm security heat. (It is
possible that safety heater thermal be triggered due to a stoppage of water flow).
- Close the door connecting the heater.
- Switch on the power and restart the heat pump.
In case of non-functioning heater, remove the heater and demand its replacement.