Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
↔
Excessively low temperature of heat exchanger refrigerant inlet
• The alarm code is displayed on the PCB´s display.
• The compressor stops and restarts automatically in 3 minutes.
• The alarm appears after 3 retries during 30 minutes.
– This alarm code is displayed when the Refrigerant temperature in water side heat exchanger inlet (Tp) is less than
-6ºC during 3 seconds. (Only for cooling operation).
– The Refrigerant temperature in water side heat exchanger inlet (Tp) is less than -20ºC during 10 seconds. (Only for
defrosting operation). No retry during defrosting operation. Alarm stop immediately.
PCB monitoring position: PCB2, Cn14
retry code: P- 06
Is the connector CN14 on the
PCB2 correctly connected?
Plug correctly and repair
wiring
No
Yes
Measure the temperature
of the position where the
water side heat enchanger
refrigerant inlet thermistor
attached, by surface
thermometer.
Is the temperature measured
and shown in segment
proper?
Yes
Check the water flow rate
(Check temperature of inlet and outlet)
No
Clogging of water strainer
Check pump reverse rotation
Check the air mixing
Are the connectors between
PCB1 and PCB2 correctly
connected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Wiring check, Repair.
(Breaking of wire, wrong
wiring)
Yes
Shortage of Refrigerant/ Gas leakage
Clogging of plate heat exchanger
Clogging of expansion valve and strainer
Pull out connector
and measure thermistor
resistance.
Is resistance correct?
No
Replace thermistor
Yes
Check PCB2
Check water temperature
(Not excessively Low)
Malfundtion of check valve
Malfunction of expansion valve