Troubleshooting
Service Manual
190
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Alarm code
description
1
failure of water outlet temperature thermistor
• The alarm code is displayed on the PCB´s display.
– This alarm code is displayed when the water outlet temperature thermistor is short circuited or cut.
PCB monitoring position: PCB2, Cn13
Are the connectors between
PCB1 and PCB2 correctly
connected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Yes
Pull out connector
and measure thermistor
resistance.
Is resistance correct?
No
Replace thermistor
Yes
Is connector CN13 on
PCB2 correctly connected?
No
Yes
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Check PCB1 and PCB2
Measuring the thermistor resistance value:
Thermistor characteristics
Temperature (ºC)
Thermistor
Resistance (k
Ω
)
note
Measure the resistance at least in 2 different points which the temperature is different more than 10 ºC.
-