Troubleshooting
Service Manual
192
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Alarm code
description
↔
1
Activation of freeze protection control (water outlet)
• The alarm code is displayed on the PCB´s display.
– This alarm code is displayed when the chilled water temperature is lower than 2ºC.
PCB monitoring position: PCB2, Cn13
Is connector CN13 on the
PCB2 correctly connected?
Wiring Check
(Breaking of wire, wrong
wiring)
No
Yes
Is the actual water
temperature and the
temperature shown in
segment proper?
Yes
No
Check pump reverse rotation
Check water strainer clogging
Check air mixing
Are the connectors between
PCB1 and PCB2 correctly
connected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Wiring check, Repair.
(Breaking of wire, wrong
wiring)
Yes
Pull out connector
and measure thermistor
resistance.
Is resistance correct?
No
Replace thermistor
Yes
Check PCB1 and PCB2
Check the water flow rate
(Check temperature of Outlet)
Check 4-way valve