Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
failure of discharge gas pressure sensor (open/Short)
• The alarm code is displayed on the PCB´s display.
– This alarm code is displayed when the high pressure sensor is short circuited or cut.
PCB monitoring position: PCB1, Cn4
Is the high pressure sensor
correctly connected to
connector CN4 on PCB1?
No
Yes
Yes
No
Is high pressure sensor
output character and low
pressure sensor display value
"Ps" proper during compressor
stop?. (See table about
sensor characteristics)
Is the voltage between
VCC05T and GND1 on
PCB1 5V?
(Refer to voltage test position)
Yes
No
Failure of power supply circuit
on PCB1. Replace PCB1.
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Failure of high pressure sensor.
Replace high pressure sensor.
Failure of component on PCB1.
Replace PCB1.
Characteristics of high pressure sensor
DCV
1 2 3
CN4
Pressure (MPa)
Output
(PCB1)
High Pressure Sensor
(0~5V) Voltage meter
Red
(+Power
Supply)
White (Out)
Black (Gnd)
note
In case that the low pressure is higher than 2.2 MPa, segment shows 2.2 MPa.
-
In this case, connect a pressure gauge to high pressure check joint, check the pressure shown in the gauge.
-