Troubleshooting
Service Manual
200
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Alarm code
description
8
failure of suction gas pressure sensor (open/Short)
• The alarm code is displayed on the PCB´s display.
– This alarm code is displayed when the low pressure sensor is short circuited or cut.
PCB monitoring position: PCB1, Cn3
Is the high pressure sensor
correctly connected to
connector CN4 on the PCB1?
No
Yes
Yes
No
Is low pressure sensor
output character and high
pressure sensor display value
"Pd" proper during compressor
stop?. (See table about
sensor characteristics)
Is the voltage between
VCC05T and GND1 on
PCB1 5V?
(Refer to voltage test position)
Yes
No
Failure of power supply circuit
on PCB1. Replace PCB1.
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Failure of low pressure sensor.
Replace low pressure sensor.
Failure of component on PCB1.
Replace PCB1.
Is the low pressure sensor
correctly connected to
connector CN3 on the PCB1?
No
Yes
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Characteristics of low pressure sensor
DCV
1 2 3
CN3
Pressure (MPa)
Output
(PCB1)
Low Pressure Sensor
(0~5V) Voltage meter
Red
(+Power
Supply)
White (Out)
Black (Gnd)