Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
Incorrect operation
• The alarm code is displayed on the PCB´s display
– This alarm code is displayed when wrong settings is performed in DIP switch on PCB or prohibited operation is
performed.
No
Is the alarm activated and
unit stopped during operation?
Turn OFF the power and set
the DIP switches correctly
Yes
Due to incorrect operation,
the unit gets stopped by the
alarm action.
Do not perform it.
No
It is changed to setting mode
during operation?
Unit is normal.
Do not change to setting
mode during operation
Failure of PCB1
Yes
Is the setting of DIP switches
correct?
Failure of DIP switch on PCB1
Is the alarm activated just
after the Power Supply is
turned ON?
Is the alarm reseted by the
stop operation?
No
No
Yes
Yes
Yes
No
Failure of PCB1