Troubleshooting
Service Manual
204
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Alarm code
description
failure of the current sensor for "Inverter" (0 A detection)
• The alarm code is displayed on the PCB´s display
• The compressor stops and restarts automatically in 3 minutes.
• The alarm appears after 3 retries during 30 minutes.
– This alarm code is displayed when the frequency of the compressor is maintained at 15~18 Hz after the compressor
is started, one of the absolute values of the running current at each phase U+, U-, V+ and V- is less than 1.5A
(including 1.5A).
retry code: P-17
warning
Electrical hazard. Risk of electrical shock. Before checking and replacing the inverter parts perform the high
-
voltage discharge procedure by referring to section "Checking procedure for main parts".
How is the compressor
operation when you restart
the compressor?
No
Are the outputs of the ISPM
and/or DIP-IPM correct?
No
Yes
Is the coil resistance of the
compressor normal?
Restart the operation
Replace the ISPM or DIP-IPM
Replace the ISPM or DIP-IPM
Compressor does not
operate.
P17 is displayed
The compressor stops
inmediatelly.
(nearly 18Hz)
Power supply cables for the
compressor are not passing
through CT. Pass the wires
through CT.
Replace the compressor