Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Turn OFF power, diconnect
U,V,W from compressor
terminals and restart. Does the
protecting function activate?
*1)
Yes
Yes
Yes
Replace ISPM or DIP-IPM
Check ISPM or DIP-IPM
Has been there any
instantaneous drop of
voltage?
No
No
No
Check compressor
Check power supply and
wiring capacity
Replace ISPM or DIP-IPM
A
*1): Turn ON the No.1 switch of the DIP switch on ISPM when restarting with disconnecting the terminals of the compressor.
After troubleshooting, turn OFF the No.1 switch of the DIP switch on ISPM.