209
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
Increase in the inverter fin temperature
• The compressor stops when the temperature of the thermistor for inverter fin excess 100ºC, and restarts automatically
in 3 minuntes.
• The alarm appears after 3 retries during 30 minutes.
retry code: P-17
1*): Perform the high voltage discharge work by referring to the section "Checking procedure for main parts" before
checking and replacing the inverter components.
No
Replace the dipIPM or
ISPM. *1)
Restart the operation.
Does it trip soon?
Yes
Remove the clogging
Is the air side heat
exchanger of the
outdoor unit clogged?
Faulty Dip IPM or ISPM, or
thermistor.
Replace it.
No
Is thermistor short circuit or
faulty?
No
Yes
Replace the thermistor
Yes