211
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Troubleshooting
Service Manual
7
Alarm code
description
no feed back signal from water pump
• The alarm code is displayed on the PCB´s display.
• It is available once feedback signal confirmed.
– This alarm code is displayed when the Pump operation feedback signal (terminals 1-2) is OFF during pump interlock
(CMp) ON (terminals 3-4).
PCB monitoring position: PCB1, PCn4
Is thermal relay for pump
(TRP) activated?. (If used a
field supplied pump)
Yes
No
Is 220-240V the voltage
between connector PCN4
PIN1 and PIN3 on PCB1?
No
Yes
Check Printed Circuit Board
(PCB1)
Check the Pump Lock
Check thermal relay for pump
Check wiring around pump
and thermal relay for pump