Troubleshooting
Service Manual
212
Troubleshooting procedure
SMGB0066 rev.0 - 12/2009
Alarm code
description
Cooler water failure (this alarm is not available in this unit)
– This alarm code is displayed when the contact between #1 and #2 of CN6 is not closed.
PCB monitoring position: PCB1, Cn6
Are the connectors between
PCB1 and PCB2 correctly
connected?
PCB1
CN9-CN1
PCB2
CN5-CN2
CN6-CN3
CN2-CN4
No
Yes
Is the voltage between
VCC24N and GND2 on PCB1
24V?
(refer to voltage test position)
Yes
Replace PCB1
Is the connector CN6 on
PCB1 correctly connected?
No
Yes
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Wiring check, Repair.
(Breaking of wire, wrong wiring)
Replace transformer
Yes
No
Check wiring and connector
Is the wiring of transformer
breaking?
Failure of power supply circuit
on PCB1
Yes
Yes
Is the voltage output of the
transformer secondary side
correctly output?
No